Live Cable Identification Instrument

Live Cable Identification Instrument

The Live Cable Identification Instrument is a professional tool designed for power cable engineers and technicians to accurately identify target cables among multiple lines. Its core functionality utilizes pulse - encoded current signals and electromagnetic field detection technology, ensuring operational safety during cable maintenance, repair, or renovation by preventing accidental cuts to live cables.
Send Inquiry
Description
Technical Parameters

Product Overview & Application Scenarios

 

Product Overview

The Live Cable Identification Instrument is a professional tool designed for power cable engineers and technicians to accurately identify target cables among multiple lines. Its core functionality utilizes pulse - encoded current signals and electromagnetic field detection technology, ensuring operational safety during cable maintenance, repair, or renovation by preventing accidental cuts to live cables.

 

Applications

De - energized Cable Identification: Exclusively for identifying de - energized cables. Never connect to live cables.

Power Maintenance: Suitable for cable identification in substations, distribution rooms, underground cable tunnels, and similar environments.

Complex Conditions: Capable of identifying thick cables and irregularly shaped conductors, even in harsh on - site environments.

 

Key Features & Advantages

 

High - Precision Identification

Utilizes PSK technology and pulse-coded current signals with directional detection to ensure precise identification.

Receiver features dynamic color raster display (green/red indicators for target/non - target cables) for intuitive operation.

Safety & Efficiency

Non - contact flexible current clamp (Rogowski coil) supports cables up to φ200mm inner diameter without disconnecting lines.

Receiver integrates AC 0V–600V voltage detection for dual - layered safety assurance.

Durable & Portable

Transmitter adopts polypropylene toolbox design, resistant to 200kg pressure, high temperatures, and abrasion.

Lightweight receiver (370g) with 3.5 - inch true - color screen, ideal for extended outdoor operations.

 

Operating Conditions

 

Environmental Requirements

Temperature: - 10℃ to 40℃ (operating), - 20℃ to 50℃ (storage).

Humidity: <80% RH (operating), ≤95% RH non - condensing (storage).

Power Requirements

Transmitter Voltage: 11.1V±1.5V.

Receiver Voltage: 7.4V±1V.

Operational Requirements

Ensure cables are centered within the clamp and avoid strong electromagnetic interference.

 

Additional Information

 

Accessories
Transmitter, Receiver, Flexible Current Clamp, Charger, Toolbox.
Warranty & Support
1 - year warranty with technical consultation and repair services.
Precautions
Never use on live cables-strictly for de - energized environments.
Store in dry conditions; avoid battery over - discharge during long - term storage.

 

Maintenance & FAQs

 

Q: What if the battery drains quickly?

A: Transmitter & Receiver: 8-hour battery life. USB-rechargeable receiver alerts when voltage drops below 6.5V. Recharge promptly when low.

Q: The clamp won't close around the cable.

A: Check if the cable exceeds φ200mm. For oversized cables, contact the manufacturer for custom clamps.

Q: How to resolve unstable signals?

A: Ensure the cable is centered, avoid EMI sources, and check transmitter battery level.

Q: How to store the device long - term?

A: Store in dry conditions (humidity ≤95%) at -20℃ to 50℃. Maintain battery at 50% charge.

Q: Receiver screen displays abnormally.

A: Restart the device. If unresolved, contact after - sales service for diagnostics.

 

Tip: Always read the manual and follow safety protocols before use!

 

Optimized for Google SEO: Keywords include cable identification tool, Rogowski coil clamp, non - contact voltage detector, high - precision cable identifier, and de - energized cable safety.

 

Hot Tags: live cable identification instrument, China live cable identification instrument manufacturers, factory, Variable Frequency Power Supply, AC Test Transformer Dry Type, Multi Frequency Voltage Test Set, Capacitor Divider Of Resonant Test Set, Container AC Resonant Test System, Water cooled Generator Insulation Resistance Tester

Technical Specifications

 

Transmitter

Power: 11.1V Li - ion battery (8 - hour runtime).

Output: 500V pulse voltage, 30A max current, 1Hz frequency.

Dimensions: 320×275×145mm; Weight: 2.5kg.

Display: 128×75mm LCD with real - time battery and signal status.

Receiver

Power: 7.4V Li - ion battery (8 - hour runtime).

Display: 3.5 - inch true - color screen with dynamic raster signal strength.

Voltage Detection: AC 0.01V–600V, ±1% accuracy.

Dimensions: 207×101×45mm; Weight: 370g.

Flexible Current Clamp

Type: Rogowski coil with transient tracking capability.

Inner Diameter: φ200mm (compatible with thick or irregular conductors).

Detection Range: 0Ω–2kΩ loop resistance (requires transmitter voltage ≥10V at 2kΩ).