The instrument is used to check the correctnessof the transformer turns ratio,the condition of the tap changer,whether the transformer is short-circuited between turns,and whether the transiomer can be operated in parallel. The three-phase output voltage is adopted to improve the test speed,The angle between phases can be measured,and the wiring group 0-11 can be automatically identified.For low-voltage rectifier transformers with multiple winding,the low-voltage side does not need lobe disconnected to measure the transformation ratio and 7.5°Angle deviation.
Send Inquiry
Description
Technical Parameters

Product Overview & Application Scenarios

 

Product Overview

The instrument is used to check the correctnessof the transformer turns ratio,the condition of the tap changer,whether the transformer is short-circuited between turns,and whether the transiomer can be operated in parallel.
The three-phase output voltage is adopted to improve the test speed,The angle between phases can be measured,and the wiring group 0-11 can be automatically identified.For low-voltage rectifier transformers with multiple winding,the low-voltage side does not need lobe disconnected to measure the transformation ratio and 7.5°Angle deviation.Adopts 7-inch high-definition color touch screen LCD,modular display,clear display even under strong light.The instrument not only has print output,U disk interface,but also RS232 interface,which is convenient for paperless office.

 

 

Features & Advantages

 

1.The coaxial precision inverter power supply is usedinside the instrument,which eliminates the influenceof harmonics ofthe mains voltage during themeasurement,and the measurement is moreaccurate.When the working power source is agenerator,there is no influence.
2.The three-phase output voltage is adopted to improve the test speed.The angle between phases can be measured,and the wiring group 0-ll can be automatically identified. For low-voltage rectifier transformers with multiple windings,the low-voltage side does not need to be disconnected to measure the transformation ratio and 7.5°Angle deviation.
3.lt is suitable for a wide variety of transformers,especially suitable for the measurement of Z-type transformers,rectifier transformers,grounding transformers,electric furnace transformers,phase-shifting transformers,balance transformers,etc,
4.With high and low voltage reverse connection protection,transformer turn-to-turn short-circuit protection,tap switch failure protection,output full short-circuit protection,and increase the stability other instrument.
5.After inputting the rated parameters,it can automatically measure the transformer ratio,error value and tap position of the tap changer.Especially for tap changers with asymmetric tapping,the accurate position of the tap changer of the transformer can also be accurately measured.A tap switches capable of measuring 99 tap positions.
6.Adopts 7-inch high-definition color touch screen LCD,modular display,clear display even under strong light.
7.The instrument not only has print output,U disk interface,but also RS232 interface,which is convenient for paperless office.
8.High quality multifunctional engineering plasticbox is cold-resistance,high temperature resistance,water proof,shake proof,which is suitable for field test.
9.By downloading APP(Android),users can control instruments,store and upload test data for easy reference.

 

Application Conditions

 

Environmental Conditions

Temperature:0°C to 50°C (operating range)

Humidity:<85% RH (non-condensing)

Altitude:<2000 meters above sea level

 

Safety Precautions

Transformer Condition:

Must be fully de-energized, isolated, and grounded

Discharge windings and bushings before testing

Personal Protective Equipment (PPE):

Insulated gloves and safety goggles

Flame-resistant clothing in high-risk environments

Work Area Safety:

Clearly mark testing zones with warning signs

Restrict access to unauthorized personnel

Power and Equipment Setup

Tester Power Supply:

AC 100–240V ±10%, 50/60 Hz, or DC power (if battery-operated)

Stable voltage without fluctuations or surges

Grounding:

Reliable earth ground connection mandatory for safety and accuracy

Test Leads and Connections:

Use manufacturer-approved leads and connectors

Ensure clean, secure connections to transformer terminals

Follow color-coding (HV: red, LV: black, ground: green)

 

Maintenance FAQs

 

Q: When Should TTR Testing Be Performed?

A:

During manufacturing– Quality control

After installation– Commissioning checks

Routine maintenance– Annually or per utility schedules

After faults– Lightning strikes, short circuits, or overloads

Post-repair/rewinding– Validation of workmanship

Q: How is the Test Performed?

A:

De-energize, isolate, and ground the transformer.

Connect the TTR tester to HV and LV windings.

Apply a low AC voltage to one winding.

Measure the induced voltage in the other winding.

Calculate the ratio: TTR = V_HV / V_LV.

Q: What Does a "Failed" TTR Test Indicate?

A:

Deviations from the expected ratio may signal:

Shorted turns:Ratio lower than nameplate value.

Open circuit:Infinite or erratic ratio.

Tap changer issues:Inconsistent ratios across taps.

Winding damage:Due to mechanical stress or overheating.

Q: Can TTR Test Three-Phase Transformers?

A:Yes. Modern testers support single-phase and three-phase testing, including automatic vector group identification (e.g., Delta-Wye configurations).

Q: What Safety Precautions Are Required?

A: Ensure the transformer is fully de-energized and grounded.

Wear insulated gloves and safety goggles.

Use properly rated test leads and connectors.

Follow lockout/tagout (LOTO) procedures.

Hot Tags: new transformer turns ratio, China new transformer turns ratio manufacturers, factory

Technical Specifications

 

1.Test Range:0.9~10000angle:0-360

2.Accuracy:±0.1%+2wrods (0.9~500)

+0.2%+2words(501-2000)

士0.5%+2words(2001-10000)

3.Angle Accuracy: ±0.2°

4.Best Resolution: ratio--0.0001angle--0.01°

5.Output voltage: Automatically adjust according toload

6.Input Power:AC220V士10% 50±1HZ

7.Temperature Range:-10'C~40'C

8.Relative Humidity: <85%, no dew.

9.Size: Instrument Caser: 360*290*170(mm),Accessories Case: 360*290*170(mm)

10.Weight:Instrument5 KGS, Accessories case 5.5KGS