500kV Cable Insulation Withstand Test System AC High Voltage Cable Testing Equipment With Partial Discharge Measurement

500kV Cable Insulation Withstand Test System AC High Voltage Cable Testing Equipment With Partial Discharge Measurement

A complete power-frequency AC withstand test station for equipment and cable insulation below 500 kV: a 200 kVA SF6 test transformer reaching 500 kV at 400 mA, driven by a compensated regulation cabinet, with a 300 pF coupling capacitor and a system partial discharge level of 1 pC at rated voltage.
Send Inquiry
Description
Technical Parameters

Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of 500kv cable insulation withstand test system ac high voltage cable testing equipment with partial discharge measurement in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.

 


Products video

 

 

Products Description

  The HMGTU-200kVA/500kV is a power-frequency AC hipot tester built around a single 200 kVA test transformer that reaches 500 kV at 400 mA. It applies an adjustable AC test voltage to cable insulation and to equipment in voltage classes below 500 kV, and it measures partial discharge on the same high-voltage circuit, specified at 1 pC at rated voltage.

The set is not one box but four cooperating parts. An operation desk, type          HMTC-200/500, runs the test sequence from a 220 V supply. An isolation, compensation and voltage regulation cabinet, type HM200kVA, conditions the incoming single-phase 380 V supply, regulates it continuously from 0 to 1000 V and supplies 200 A at its output. The SF6 test transformer steps that 1000 V to 500 kV. A capacitive divider with a quick protection box, a 300 pF coupling capacitor and an impedance matching unit complete the chain, giving the operator a measured voltage and a discharge signal for the PD detector.

  The high-voltage column is held in a sealed SF6 tank inflated to 0.5 MPa. That matters for a factory that runs the set every day: the insulating medium is filled once and then monitored by pressure, rather than handled, filtered and sampled as an oil volume would be. Each sealed chamber is specified to leak less than 0.5% of its gas per year, and the manual states the tank pressure during normal testing is held at 0.5 MPa within 5%.

Everything the operator touches is on the low-voltage side. The desk sets the test voltage, the withstand time, the boost and step-down rates, the alarm thresholds and the flashover factor; the cabinet does the switching; the high-voltage end is left to the transformer and the divider.

 

logo5

200 kVA rated

 

500 kV / 400 mA

 

PD ≤1 pC

 

Divider accuracy 1.5%

 

 

 

Key features

 

 

competitive advantage
 

500 kV from a 200 kVA column

Rated capacity 200 kVA, rated high voltage 500 kV, rated high-voltage current 400 mA at 50 Hz.

Gas insulation, sealed for life

The 500 kV winding sits in an SF6 tank at 0.5 MPa; each sealed chamber leaks less than 0.5% per year.

1 pC at rated voltage

The transformer is specified at 1 pC, and the complete system is specified below 1 pC at rated voltage with the supply harmonic component under 5%.

50 kVA in, 200 kVA out

The cabinet draws 50 kVA at 131.5 A and delivers 200 kVA at 1000 V / 200 A, using a bank of eight 25 kVA / 400 V compensation reactors.

 

 

Divider and coupling capacitor in the set

A capacitive divider with 1.5% accuracy and a 300 pF coupling capacitor with impedance matching unit for PD acquisition.

Programmable test cycle

Test voltage, withstand time, boost and step-down speeds from 100 to 3000 V/s, voltage alarm at 1.1 times the set value, and a flashover factor recommended at 30%.

Automatic or manual control

Automatic mode boosts, times and returns the voltage to zero on its own; manual mode gives push-button boost and step-down with a timing function.

Built-in interlocks

The main contactor drops out on over-voltage or over-current, and the system returns to the zero position whenever power is applied.

Technical Specifications

 

Test transformer - HMGTU-200kVA/500kV

Parameter Value
Rated capacity 200 kVA
Rated high voltage 500 kV
Rated high-voltage current 400 mA
Rated low voltage 1000 V
Rated low-voltage current 200 A
Rated frequency 50 Hz
Supply AC 380 V, 50 Hz, single phase
Insulation medium SF6
Inflation pressure 0.5 MPa
Impedance voltage Below 12%
Waveform distortion ≤3%
Partial discharge ≤1 pC at rated voltage
Metering voltage 200 V

Isolation, compensation and voltage regulation cabinet - HM200kVA

Parameter Value
Power supply Single phase, 380 V / 50 Hz
Input capacity 50 kVA
Input current 131.5 A
Output capacity 200 kVA
Output voltage 1000 V
Output current 200 A
Power insulation transformer 50 kVA / 400 V / 400 V
Electrical voltage regulator 50 kVA / 400 V
Isolation transformer 200 kVA / 400 V / 1000 V
Compensation reactor 25 kVA / 400 V × 8

Operation desk - HMTC-200/500

Parameter Value
Input voltage 220 V
Frequency 50 Hz
Control software GTU test and control system
Test voltage setting Any value up to the rated output
Withstand time ≤10 min at rated current; ≤30 min continuous at 2/3 rated current
Boost and step-down speed 100–3000 V/s, maximum
Alarm voltage 1.1 times the required test voltage
Alarm current Adjustable low-voltage current limit; main contactor trip on exceedance
Flashover factor 30% recommended; protection acts when the voltage drops beyond the set factor
Control positions Power switch and emergency stop on the left of the desk

Divider, coupling capacitor and PD chain

Parameter Value
Divider accuracy 1.5%
Coupling capacitor 300 pF
PD acquisition Impedance matching unit feeding a PD detector
Quick protection box Protects the test transformer when the specimen breaks down
Divider signal and fibre Divider signal and optical fibre routed back to the cabinet

Installation conditions

Parameter Value
Ambient temperature −10 to +40 °C
Altitude and humidity No requirement stated for fully enclosed testing equipment
Location Indoor use
Supply quality Sine wave, waveform distortion ≤3%, independent three-phase five-wire supply with earth
Earthing Reliable earth system, grounding resistance below 0.5 Ω
Discharge background Spatial partial discharge background below 1 pC
Supply harmonics Test supply harmonic component below 5%
System performance Local discharge below 1 pC at rated voltage; each sealed chamber leaks below 0.5% per year

 

 

Scope of supply

 

Item Model / rating Qty
SF6 test transformer HMGTU-200kVA/500kV 1
Isolation, compensation and voltage regulation cabinet HM200kVA 1
Operation desk with control computer HMTC-200/500 1
Capacitive voltage divider with quick protection box 500 kV class, 1.5% accuracy 1 set
Coupling capacitor with impedance matching unit 300 pF 1 set
Interconnecting leads, optical fibre, aviation-connector cables, earthing leads Matched to the set 1 set

 

 

FAQ

 

Q: How is the test voltage measured?

A: A capacitive voltage divider on the high-voltage side feeds the measuring channel, with the divider specified at 1.5% accuracy. The test transformer carries a separate 200 V metering winding for the local meter.

Q: What duty cycle does the set accept?

A: Up to 10 minutes at rated current, or continuous operation for up to 30 minutes at two thirds of rated current.

Q: What supply does the system need?

A: What supply does the system need?