AC Series Resonance Test Set

AC Series Resonance Test Set

14040kVA-130kV Series Resonant Test is primarily designed and manufactured for AC withstand voltage testing of 110kV and 220kV cables, power transformers, and all principal electrical equipment within 220kV power systems. The reactors employ a multi-unit, separate design to meet the testing requirements for high-voltage, low-current equipment. It serves as an ideal withstand voltage device for high-voltage testing departments at provincial, municipal, and county levels, as well as for power installation, maintenance, and testing engineering units. The apparatus primarily comprises a variable-frequency control power supply, excitation transformer, high-voltage reactors, and capacitive voltage divider.
Send Inquiry
Description
Technical Parameters

Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of ac series resonance test set in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.

 

Product Overview & Application

 

6

(1)130 kV-Suitable for 35 kV power systems; AC withstand voltage testing of transformers, insulators, high-voltage circuit breakers, and GIS

(2) Output voltage waveform distortion rate: <1.0%

(3) Permissible continuous operating time: 30 minutes of continuous operation under rated conditions; 60 minutes of continuous operation during cable withstand voltage testing

(4) Device quality factor: Q > 50

(5) Quality factor under full load during cable testing: Q > 30 (load-dependent)

(6) Input power supply: Three-phase 380 V

(7) Frequency adjustment range: 30 Hz to 300 Hz

(8) System measurement accuracy: 1.0%

(9) The device features protection functions such as overvoltage, overcurrent, and zero-position start

 

 

Features & Advantages

 

Feature:

  • Significantly reduced power supply capacity requirements.
  • Substantially diminished equipment weight and volume.
  • Improved output voltage waveform.
  • Prevents large short-circuit currents from burning the fault point.
  • No recovery overvoltage occurs.

 

Advantage:

The unit incorporates protection functions against overvoltage, overcurrent, zero-position start-up, system detuning, and high-voltage flashover faults.

The entire unit is lightweight, facilitating on-site deployment.

The unit offers four operational modes, enabling flexible selection based on site conditions to enhance testing efficiency. Modes include: Fully Automatic Mode, Manual Mode, and Automatic Tuning with Manual Voltage Increase Mode.

Capable of storing, printing on-site, and remote printing of data.

Utilises DSP platform technology, facilitating easy functional expansion, reduction, and upgrades according to user requirements.

 

Technical Parameters

 

(1) Variable Frequency Power Supply CHXB-700kW/380V

a) Rated Output Capacity: 700 kW

b) Input Power Supply: Three-phase 380 V, 50 Hz

c) Output Voltage: 0–400 V, single-phase, 20–300 Hz

d) Rated Input Current: 1063.5 A

e) Rated Output Current: 1750A

f) Output Waveform: Sine wave

g) Voltage Resolution: 0.01kV

h) Voltage Measurement Accuracy: 0.5%

i) Frequency Adjustment Range: 20 – 300Hz

j) Frequency Adjustment Resolution: ≤0.1Hz

k) Frequency Stability: 0.1%

l) Operating time: 60 min continuous operation at rated capacity

m) Maximum component temperature during 60 min continuous operation at rated capacity: ≤65K

n) Noise level: ≤50 dB

(2) High-voltage reactor DK-2340kVA/130kV 6 sections

a) Rated capacity: 2340kVA

b) Rated voltage: 130kV

c) Rated current: 18 A

d) Inductance: 30 H/section

e) Inductance tolerance: ±5%

f) Quality factor: Q ≥ 50 (f = 45 Hz)

g) Frequency: 30 – 300 Hz

h) Enclosure type: Oil-immersed with insulating cylinder

i) Cooling method: ONAN

j) Maximum temperature rise: ≤65K

k) Operating time: Rated output current, continuous for 60 min

l) Noise level: ≤60 dB

m) Lifting method: Lifting eyes + hooks

(3) Excitation transformer JLB-700kVA/3kV/4kV/5kV/6kV/0.4kV

a) Rated capacity: 700kVA

b) Input voltage: 400V

c) Output voltage: 3kV; 4kV; 5kV; 6kV

d) Output current: 233.3A; 175A; 140A; 116.7A

e) Voltage drop: ≤10%

f) Noise level: ≤60dB

g) Operating time: Rated output current, continuous for 60 min

h) Maximum temperature rise: ≤65K

i) Frequency: 30 – 300 Hz

j) Cooling method: ONAN

(4) Capacitive Voltage Divider FCR-150kV -1000 pF

a) Rated voltage: 150V

b) Capacitance: 1000 pF

c) Operating frequency: 30–300 Hz

d) Maximum overvoltage setting: 1.1 times the rated voltage

e) When testing non-capacitive specimens, it also serves as a resonant capacitor

f) Dielectric loss of the divider body: ≤0.5%

g) Enclosure type: Insulated cylinder

h) Cooling method: ONAN

i) Maximum temperature rise: ≤65K

j) Operating time: Rated output current, continuous for 60 min

k) Noise level: ≤60 dB

l) Measurement accuracy: Class 1.5

m) Voltage division ratio: 3000:1

 

Product images

 

 

01

02

03

04

 

Hot Tags: AC Series Resonance Test Set, China AC Series Resonance Test Set manufacturers, factory, ac resonance cable testing system for ac resonance factory testing system, ac resonance integration testing system, hv insulation tester, ac resonance device testing system for ac resonance measuring instrument, high voltage testing transformer, ac resonance performance testing instrument for systems