HM6050D Multi-Pulse Cable Fault Locator Operating Guide

Feb 11, 2026 Leave a message

 

HM6050D Multi-Pulse Cable Fault Locator Operating Guide

 

logo14

 

I.Precautions:

1. Low resistance / short circuit (<100Ω): Employ low-voltage pulse method with wave velocity 160–170m/μs and pulse width 0.1–0.2μs

2. High resistance / flashover (>100kΩ): Employ multiple-pulse method with high-voltage generator, maintaining wave velocity as above with pulse width 2μs

3. Distance-to-fault formula: Distance = Wave velocity (m/μs) × Time difference (μs) ÷ 2

4. Safety precautions: High-voltage operations must be earthed; voltage rise ≤5kV/s; single operation of multiple-pulse coupler ≤5 minutes

 

II. Fault Prediction (Using Insulation Resistance Tester)

1. <100Ω: Low resistance / Short circuit → Low-voltage pulse method

2. 100Ω–100kΩ: Medium resistance → Multiple pulse method

3. >100kΩ: High resistance / Flashover → Multiple pulse method

 

 

III.Multiple Pulse Method (High Resistance / Flashover)

1. Wiring

  • High-voltage generator → High-voltage capacitor → Multiple pulse coupler → Faulted phase core wire
  • Coupler → Host signal input terminal
  • High-voltage generator tail end → Reliably earthed
  • Cable far end: Floating

2. Host Configuration

  • Mode: Select Multiple Pulse (8 samples)
  • Wave Velocity: Same as low-voltage pulse (160m/μs)
  • Pulse Width: 2μs
  • Sampling Frequency: ≥24MHz (to ensure accuracy)

3. High-Voltage Operation

  • Power-up: Switch on host first, then high-voltage generator
  • Voltage Rise: Rate '≤5kV/s', rise to 6–8kV (not exceeding 3–5 times cable rated voltage)
  • Triggering: Press the main unit start button to initiate high-voltage discharge; fault point flashovers occur (visible sparks / audible discharge sounds)
  • Sampling: The main unit automatically acquires 8 sets of pulse waveforms; single operation ≤5 minutes (protecting the coupler)
  • Shutdown: First press the main unit stop button, then reduce voltage, switch off the high-voltage power supply, and finally switch off the main unit

4. Waveform Analysis

  • Page: Select a clear, oscillation-free M-shaped waveform
  • Cursor: Position at the incident wave start point and the reflected wave inflection point
  • Reading: Instrument displays fault distance; repeat 2–3 times and take the average
  • Error: ≤1% is acceptable