AC Resonant Test System with PD

AC Resonant Test System with PD

The AC Resonant Test System with PD (Partial Discharge) is a high - performance testing device developed by Wuhan Goldhome Hipot Electrical Co., Ltd for high - voltage electrical equipment in power systems. It is designed for AC withstand voltage tests and partial discharge detection, utilizing variable - frequency power supply to achieve resonance between inductance (L) and capacitance (C), thereby applying high voltage to test samples.
Send Inquiry
Description
Technical Parameters

Product Overview & Application

 

The AC Resonant Test System with PD (Partial Discharge) is a high - performance testing device developed by Wuhan Goldhome Hipot Electrical Co., Ltd for high - voltage electrical equipment in power systems. It is designed for AC withstand voltage tests and partial discharge detection, utilizing variable - frequency power supply to achieve resonance between inductance (L) and capacitance (C), thereby applying high voltage to test samples.

 

Features & Advantages

 

  • Enhanced Safety: Multiple protections (over - voltage, over - current, breakdown) for operator and equipment safety.
  • User - Friendly Design: Simplified wiring and microcomputer - controlled system ensure stable, intuitive operation.
  • Portability: Compact structure for easy transportation and on - site testing.
  • Low Distortion: Output sine wave distortion <1% for non - destructive testing.
  • Energy Efficiency: High output power with low input requirements, ideal for limited power supply scenarios.
  • Data Management: Data storage, query, and print functions for analysis and reporting.
  • Flexible Modes: Supports single/three - phase switching and parallel operation for diverse testing needs.
  • Self - Healing Capability: Automatic repair of partial amplifier tube failures.

 

Operating Conditions

 

  • Altitude: ≤3000m
  • Temperature: - 10℃ to 40℃
  • Humidity: ≤95% (at 25℃)
  • Storage Temperature: - 20℃~50℃
  • Humidity: ≤95%
  • Environment: Free of conductive dust, explosive hazards, corrosive gases; reliable grounding; tilt ≤5°.

 

Maintenance & Troubleshooting

 

Routine Maintenance:

Regularly inspect wiring and tighten connections.

Keep the device clean and dry to prevent dust accumulation.

Secure equipment during transport with dedicated straps.

Discharge capacitors fully before servicing.

 

Common Issues & Solutions:

  • Power Indicator Off: Check if the circuit breaker is closed or press the panel's power button.
  • Control Interface Failure: Ensure power and communication links (fiber/wireless) are active; reboot.
  • Tripped Circuit Breaker: Disconnect output filter 1P breaker; use non - leakage - protected breakers.
  • HV Measurement Box Setup: Turn off measurement switches in the calibration interface, save settings, and restart.
  • "Overload Protection" Alert: Reduce excitation transformer ratio (adjust taps) to minimize losses.

 

Hot Tags: ac resonant test system with pd, China ac resonant test system with pd manufacturers, factory, primary current injection test set, Capacitor Divider Of Resonant Test Set, 1800kV 180kJ Lightning Impulse Voltage Generator, Impulse Winding Tester Withstand Voltage Tester, AC Resonant Test Set, Ultra light AC Test Transformer

Technical Specifications

 

  • Input Power: 3 - phase AC 380V±10%, 50Hz
  • Output Voltage: Line voltage 0~350V (continuously adjustable)
  • Output Current: Max. 857A (resistive load)
  • Output Power: 300kW
  • Frequency Range: 20~300Hz; precision ±0.1Hz
  • Continuous Operation: 180 minutes at full load
  • Partial Discharge: ≤10pC
  • Noise Level: <85dB