Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of insulator zero-value detector in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.
Products Video
DH-18D Insulator Zero-Value Tester Display Video
Product Overview

The DH-18D Insulator Zero-Value Tester is primarily employed for detecting concealed faults within 35–1000kV suspension insulators or for laboratory testing of suspension insulators. It can measure the distributed voltage or insulation resistance of each insulator under live (or de-energised) conditions, to assess the condition of insulators. This facilitates the timely replacement of insulators with non-compliant distribution voltage or insulation resistance values, thereby ensuring the reliable and safe operation of transmission lines.
product parameters
1. Resistance measurement resolution: 1MΩ
2. Sampling rate: 10 times per second
3. Display method: Handheld unit LCD display
4. Maximum transmission distance: 100 metres
5. Power supply: One 3.7V rechargeable lithium battery each for transmitter and receiver
6. Charging time: Approximately two hours
7. Operating time: 10 hours continuous operation on full charge
8. Operating temperature: 0°C to 40°C
9. Storage temperature: -10°C to 50°C
10. Relative humidity: <85%
11. Compatible insulated pole: 5-metre telescopic insulated pole (customisable)
12. Instrument aluminium alloy case dimensions:
370mm × 310mm × 115mm
13. Instrument weight: 2.5kg

Products structures

troubleshooting
|
S/N |
Abnormal Phenomenon | Cause | Remedy |
|
1 |
Handheld unit fails to power on |
1,Instrument hardware fault. 2,Instrument voltage too low. |
1,Return for factory repair. 2,Recharge. |
|
2 |
Transmitter unit fails to power on |
1,Instrument hardware fault. 2,Instrument voltage too low. |
1,Return for factory repair. 2,Recharge. |
|
3 |
Handheld unit fails to receive signal |
1,Instrument hardware fault. 2,Distance too great 3,Signal obstructed by objects 4,Transmitter unit frozen |
1, Return for factory repair. 2,Reduce distance. 3,Avoid obstructions. 4,Restart unit. |
|
4 |
Handheld unit displays incorrect signal |
1,Incorrect test mode |
Press the power switch on the handheld unit |
Hot Tags: insulator zero-value detector, China insulator zero-value detector manufacturers, factory