Product Video
SF6 Gas Comprehensive Analyzer Operation Video
Products Description

SF6 comprehensive analyzer is specially used for index detection of insulating gas in SF6 electrical equipment, and adopts the high-performance sensor for measurement of dew point, purity and decomposition product to guarantee the accurate and stable test results. Equipped with the unique gas circuit structure, it adopts the high-precision electronic flowmeter for full-automatic detection so that the SF6 can be more accurate in gas analysis. Three indexes can be detected via one-time measurement, which greatly reduces the workload of users and improves the work efficiency
Key Features & Advantages
- Dual-channel flow control design without fear of pressure fluctuation
- Utilization þf high-precision electronic flowmeter, with flow overruns prompt
- Switch of trends of measuring objects, and real-time display of data
- .Self-calibration function of zero and slope after startup
- Crossing-resistance interference technology of sensor
- Cleaning of residual gas in air circuit
- Lithium battery with ultra-large capacity, and dual purpose of AC / DC
- Large-capacity data storage, and USDB one-key data export
- Thermosensitive mute printer for rapid printing on the scene.

Technical Parameters
SF6 gas decomposition product detection module
|
Measurement scope |
[SO2]0~100 µl/l, [H2S]0~100 µl/l, [CO]0~1000 µl/l |
|
Precision |
SO2, H2S: ±0.5µl/l if measurement value ≤10 µl/l; ±5% if measurement value >10 µl/l CO: ±2.0 if measurement value ≤50 µl/l ±4% if measurement value >50 µl/l |
|
Repeatability |
SO2, H2S: ±0.2 µl/l if measurement value ≤10 µl/l; ±2% if measurement value >10 µl/l CO: ±1.5 µl/l if measurement value ≤50 µl/l; ±3% if measurement value >50 µl/l |
|
Resolution |
SO2, H2S, CO: 0.1 µl/l |
|
Response time |
≤30s |
SF6 purity detection module
|
Measurement scope |
0~100% |
|
Precision |
≤±0.5% (90~100%:≤±0.2%) |
|
Repeatability |
≤±0.2% |
|
Resolution |
0.01% |
|
Response time |
≤30S |
SF6 humidity detection module
|
Dew point range |
―80℃~+20℃ |
|
Measurement accuracy |
±0.5℃ |
|
Micro-water scope |
0.05~23100 μL/L |
|
Measurement response time (+20℃) |
-60℃ →20℃ 5S[10s] 20 ℃→-60℃ 10S[300S] |
|
Resolution |
Dew point: 0.1℃ Micro-water: 0.1ppm (100ppm~1000ppm) 0.01ppm(10ppm~100ppm) |
|
Repetition: |
±0.2℃ |
Flow regulation 1: 0.2L/min; Flow regulation: 2:0.5-0.6L/min
Parameters of whole machine
|
Charging source |
220VAC±10% 50HZ |
|
Battery |
Lithium battery 12V 17.5AH |
|
Service time |
>10h |
|
Display screen |
7-inch color touch screen |
|
Sample gas pressure |
≤1.0Mpa |
|
Size |
467×372×177mm |
|
Weight |
About 8.5kg |
Hot Tags: sf6 multi-function analyzer, China sf6 multi-function analyzer manufacturers, factory
Technical Specifications
|
Measurement Items |
Details |
|
SF6 Purity |
Range: 0%~100% |
|
Accuracy: ±0.5% |
|
|
Response Time: 15s (90% reading) |
|
|
H₂S |
Range: 0–200μL/L |
|
Detection Limit: ≤0.1ppm |
|
|
Response Time: ≤5 minutes |
|
|
SO₂ |
Range: 0–200μL/L |
|
Resolution: ±0.5μL/L (low) |
|
|
Accuracy: ±1μL/L (≤10μL/L) |
|
|
CO |
Range: 0–1000μL/L |
|
Resolution: ±5μL/L (low) |
|
|
Accuracy: ±4μL/L (≤50μL/L) |
|
|
HF (Optional) |
Range: 0–10μL/L |
|
Detection Limit: ≤0.1ppm |
|
|
Resolution: ±0.05μL/L (low) |
|
|
Environmental Adaptability |
Temp: - 30℃ to +50℃ |
|
Humidity: 0–100% RH |
|
|
Max Pressure: ≤1MPa |
|
|
Power & Battery |
Input: AC 100–240V |
|
Battery: 12h runtime |
|
|
Charging Time: 10h |
|
|
Physical Parameters |
Dimensions: 280×190×300 mm |
|
Weight: 7.6kg |