Product Overview & Application Scenarios
Product Overview
The HM5006 Transformer Dielectric Loss Tester is a specialized, high-precision instrument designed for diagnosing the condition of insulation in high-voltage electrical apparatus, primarily power transformers and other equipment like bushings, current transformers (CTs), and voltage transformers (VTs).HM5006 is to measure the Dielectric Loss Factor (tan δ) and Capacitance (Cx) of insulation systems. It is specifically used to assess the condition of insulation in transformers, bushings, circuit breakers, and other high-voltage apparatus. The device helps in identifying insulation degradation, moisture ingress, and aging, thereby preventing unexpected failures.
Features & Advantages
1. Large LCD display
2. Mass storage data
3.Multiple test modes
4.CVT test step in place do not dismantle the high-voltage lead measurement CVT
5.CVT reverse shield method for measuring C0
6. High speed sampling signal
7.Multi protection security
additional Information
|
Category |
Item |
Quantity |
Notes |
|---|---|---|---|
|
Main Unit |
HM5006 Tester |
1 |
|
|
Cables |
High-Voltage Output Cable |
1 |
Shielded, heavy-duty |
|
Measurement Cable (Cx) |
1 |
Low-loss, with clips |
|
|
Ground Cable |
1 |
Thick, braided |
|
|
Power & Data |
AC Power Cord |
1 |
For main power |
|
PC Communication Cable |
1 |
Typically USB |
|
|
Software |
1 |
CD or USB drive |
|
|
Safety |
Discharge Rod |
1 |
With insulated handle |
|
Alligator Clips/Probes |
Set |
For various connections |
|
|
Case & Docs |
Protective Carrying Case |
1 |
With custom foam |
|
User Manual |
1 |
||
|
Calibration Certificate |
1 |
Maintenance FAQs
Hot Tags: transformer dielectric loss tester, China transformer dielectric loss tester manufacturers, factory, electrical test competitiveness testing, electrical test marketability testing, electrical test profitability testing
Technical Specifications
|
1 |
Use conditions |
-15℃~40℃ |
RH<80% |
|||
|
2 |
Anti-interference |
Frequency conversion |
||||
|
3 |
Power |
AC 220V±10% |
Allowable generator |
|||
|
4 |
High output |
0.5KV~10KV |
Every 0.1kV |
|||
|
Precision |
2% |
|||||
|
Maximum current |
200mA |
|||||
|
Capacity |
2000VA |
|||||
|
5 |
Self-excited power |
AC 0V~50V/15A |
45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Automatic double frequency |
|||
|
6 |
Resolving power |
tgδ: 0.001% |
Cx: 0.001pF |
|||
|
7 |
Precision |
tgδ:±(Reading*1.0%+0.040%) |
||||
|
C x :±(Reading*1.0%+1.00PF) |
||||||
|
8 |
measuring range |
tgδ |
Unlimited |
|||
|
C x |
15pF < Cx < 300nF |
|||||
|
|
10KV |
Cx < 60 nF |
||||
|
|
5KV |
Cx < 150 nF |
||||
|
|
1KV |
Cx < 300 nF |
||||
|
CVT test |
Cx < 300 nF |
|||||
|
9 |
CVT range |
10~10000 |
||||
|
accuracy |
0.1% |
|||||
|
Resolving power |
0.01 |
|||||
|
10 |
Exterior dimension |
350(L)×270(W)×270(H) |
||||
|
11 |
Memory size |
The 200 group supports U disk data storage |
||||
|
12 |
Weight |
28 Kg |
||||