1600kV Lightning & Switching Impulse Generator

1600kV Lightning & Switching Impulse Generator

This equipment is a high-voltage impulse test system primarily used for standard lightning impulse full-wave, operating-wave, and truncated-wave impulse voltage tests on test specimens such as air gaps, suspension glass insulators, composite insulators, and bushings. The equipment features an 8-level H-type four-column tower structure (based on German HighVolt technology), with a rated voltage of ±1600 kV and a rated energy of 160 kJ. It is suitable for indoor use and complies with numerous national and international standards, including GB, DL, and IEC.
Send Inquiry
Description
Technical Parameters

Product Overview 

 

1600kV02

 

 

This equipment is a high-voltage impulse test system primarily used for standard lightning impulse full-wave, operating-wave, and truncated-wave impulse voltage tests on test specimens such as air gaps, suspension glass insulators, composite insulators, and bushings. The equipment features an 8-level H-type four-column tower structure (based on German HighVolt technology), with a rated voltage of ±1600 kV and a rated energy of 160 kJ. It is suitable for indoor use and complies with numerous national and international standards, including GB, DL, and IEC.

 

 

product Parameter

 

1600kV05

 

 

  • Nominal Voltage ±1600 kV
  • Rated Stage Voltage ±200 kV (8 stages)
  • Rated Energy 160 kJ
  • Total Capacitance 0.125 μF (2.0 μF/100 kV per unit, 16 units total)
  • Stage Capacitance 2.0 μF
  • Minimum Output Voltage ≥10% Un
  • Charging Voltage Instability ≤±1.0%
  • Synchronization Range ≥20%
  • Loss-of-Control Rate ≤2%
  • Ignition Range 10%–100% Un
  • Output Waveform Standard lightning full-wave (1.2±30% / 50±20% μs)
  • Standard truncated wave (2–6 μs)
  • Operating wave (250±20% / 2500±60% μs)
  • Voltage Utilization Factor (Lightning Full Wave) ≥90% (no load, 500 pF)
  • ≥85% (load, 2000 pF)
  • Voltage Utilization Factor (Truncated Wave) ≥85%
  • Voltage Utilization Factor (Operating Wave) ≥80%
  • Continuous Operation Capability >70% Un: one discharge every 2 minutes
  • <70% Un: one discharge every 1 minute

 

 

 

Comparison Item

 

Comparison Item 900kV/90kJ Solution 1600kV/160kJ Solution
Applicable Test Objects Switchgear, circuit breakers, load switches Insulators, bushings, air gaps
Voltage Level ±900 kV ±1600 kV
Structure H‑type (9 stages) H‑type four‑column (8 stages, German‑inspired design)
Special Features Lightning full wave + switching impulse Lightning full wave + switching impulse + chopped wave
Chopping Device None Yes (independent multi‑stage chopping gap)
Measurement System TBS2000 oscilloscope TDS 3012 (higher performance)