High Voltage Lightning Impulse Generator System

High Voltage Lightning Impulse Generator System

The HMCJ-600kV/60kJ Lightning Impulse Voltage Generator is suitable for testing the lightning full-wave and lightning impulse wave performance of high-voltage switchgear, circuit breakers, load switches, power cables, and other electrical......
Send Inquiry
Description
Technical Parameters

Products Video

 

HMCJ-600kV/60kJ Lightning Impulse Voltage Generator Display Video

 

 

 

Product Features

 

 

  • The main unit features an H-type, 6-stage tower-style modular design with symmetrical charging on both sides, ensuring easy disassembly and maintenance as well as structural stability;
  • Thyristor-controlled constant-current voltage regulation with continuously adjustable charging voltage; the charging power automatically shuts off at the moment of ignition;
  • The spark gap motor provides electric distance adjustment, supporting manual/automatic adjustment with upper and lower limit protection; the first stage features opposite-polarity triggering, while stages 2–6 use three-gap ignition, with a synchronous failure rate of <2%;
  • The leading-edge and trailing-edge resistors are inductively wound with interchangeable board configurations, include built-in storage positions, and support flexible multi-stage parallel and series combinations;
  • Fully automated control via a complete Siemens PLC system; data acquisition via an industrial PC and Tektronix oscilloscope; automatic waveform analysis, data storage, and report printing;
  • Expandable equipment mounting brackets and charging units; comprehensive protection features including overvoltage, overcurrent, automatic grounding, and emergency shutdown.

 

2

 

Products Parameters

1

  • Nominal voltage: 600 kV
  • Rated stage voltage / charging voltage: 100 kV
  • Nominal energy: 60 kJ
  • Number of stages: 6
  • Single-stage capacitance: 2.0 μF, total surge capacitance: 0.333 μF
  • Single-stage energy: 10 kJ
  • Intrinsic inductance: 55 μH
  • Minimum output voltage: >10% Un
  • Synchronization range: Stage voltage 20%–100% of rated voltage, synchronization range ≥20%
  • Synchronized discharge failure rate: <2%
  • Ignition range: 10%–100% Un
  • Charging voltage instability: ≤±3.0%
  • Voltage measurement accuracy: ≤1.0%
  • Partial response time Ta: ≤100 ns
  • Voltage division ratio accuracy: ≤±1.0%
  • Amplitude adjustment voltage error: ≤1.0%

 

FAQs

Q: Can the equipment perform tests continuously for extended periods?

A: It can operate continuously at a rate of one charge-discharge cycle every 120 seconds at 80% or more of the rated voltage; at less than 80%, it can operate continuously for extended periods.Yes. Fiber-optic communication is used between the industrial control computer and the PLC control cabinet, allowing remote operation of the isolation and grounding switches on the GTU-250/500 unit from the control room in the 1000 kV test hall.

Q: What are the configurations for the wavefront and wave-tail resistors? Are they compatible with cable testing?Does the system support remote control?

A: The standard configuration includes 3 sets of lightning wavefront resistors, 2 sets of wave-tail resistors, and 1 set of operation wave-tail resistors. Dedicated resistors can be added to support 0.4μF and 1μF power cable impulse tests.

Q: What is the charging method?

A: A bilateral symmetrical constant-current charging method is used, with thyristor-controlled constant-current voltage regulation, continuously adjustable from zero to the set voltage. The charging power supply automatically shuts off at the moment of ignition and discharge.