Parameter Description
1. Nominal voltage: 600kV
2. Rated stage voltage: 100kV
3. Rated charging voltage: 100kV
4. Nominal energy: 60kJ
5. Total impulse capacitance: 0.333F (Single pulse capacitor: 2.0F/100kV, total 6 units)
6. Stages: 6 stages
7. Stage capacitance: 2.0F
8. Stage energy: 10kJ
9.Voltage Utilization Coefficient: When load capacitance is ≤2000 pF, the voltage utilization coefficient for standard lightning waveform ≥90%, and for standard operating waveform ≥75%. When load capacitance is ≤4000 pF, the voltage utilization coefficient for standard lightning waveform ≥85%, and for standard operating waveform ≥70%.
10.Operating Duration: At voltages above 80% of rated voltage, continuous operation is possible with one charge/discharge cycle every 120 seconds. At voltages below 80% of rated voltage, continuous operation is possible.

Products Description
DC Charging Section

(1) Utilizes a thyristor constant-current voltage regulation device; rated output voltage ±100kV, rated output DC current 10-200mA;
(2) Employs an oil-immersed charging transformer with secondary voltage 50kV and rated capacity 10kVA;
(3) Utilizes 2DL-300kV/500mA high-voltage rectifier silicon stacks with reverse withstand voltage of 300kV and average current of 0.5A. The high-voltage rectifier silicon stacks are mounted on the chassis and can automatically switch charging voltage polarity via a transmission mechanism. A polarity switch conversion button is provided on the control console;
(4) Protective resistor for high-voltage rectifier silicon stack: Insulated wire wound tightly around an insulating tube;
(5) Dual-side symmetrical constant-current charging method employed;
(6) During automatic control, within the 10%–100% rated charging voltage range: Actual charging voltage deviation from setpoint ≤ ±1%, charging voltage instability ≤ ±1%, and charging voltage adjustability accuracy of 1%;
(7) One DC resistor voltage divider employs a 100kV, 200MΩ oil-immersed metal film resistor. The low-voltage arm resistor is mounted within the divider's bottom flange, with voltage signals from the low-voltage arm routed to the control console via shielded cable;
(8) The automatic grounding switch utilizes an electromagnetically operated grounding mechanism. Upon test termination, it automatically shorts the main capacitor and grounds it through the protective resistor.