Zinc Oxide Arrester Live Tester

Zinc Oxide Arrester Live Tester

YLBL‑8022 Zinc Oxide Arrester Live Tester checks zinc oxide surge arresters.You can use it with the power on or off, for any voltage level.It finds problems inside the arrester, like moisture or aging parts.
Send Inquiry
Description
Technical Parameters

Product Overview & Application Scenarios

 

YLBL‑8022 Zinc Oxide Arrester Live Tester checks zinc oxide surge arresters.You can use it with the power on or off, for any voltage level.It finds problems inside the arrester, like moisture or aging parts.

 

Key Features & Advantages

 

  • 7‑inch HD Color Touchscreen

  Big, clear 7‑inch screen (800×480). Easy to read data.

  • Long‑distance Wireless Connection

  Wireless sync. Standard range >1,500m; up to 5,000m with optional add‑ons.

  • Flexible Sync Options

4 ways to sync:

Wired (485)

Wireless

Angle‑based (no voltage needed)

Current‑analysis (uses current as voltage reference)

  • Works Anywhere

  Use it on live arresters, offline arresters, or in a lab.

  • Wide Measurement Range

Voltage: 0–250V
            Current: 0–20mA

  • 3‑Phase Simultaneous Test

Test voltage and current on all 3 phases at once - saves time.

You can also test one or two phases if needed.

 

Technical Specifications

 

Parameter

Specification

Reference Voltage Input (Peak)

10V–200V (Customizable: 0–250V)

Full Leakage Current Range

100μA–10mA (Customizable: 0–20mA)

Resistive/Capacitive Current Range

100μA–10mA (Customizable: 0–20mA)

Angle Measurement Range

0°–90°

System Accuracy

±(Reading ×5% +5 digits) (Harmonic Current ≤2mA)

Power Consumption

≤4W

Power Supply

AC220V ±10%, 50Hz ±1% (External battery option available)

Lithium-ion battery specifications Charging time > 2.5 hours
Continuous operating time > 7 hours
Intermittent operating time > 7×24 hours
Package dimensions 42 cm × 34 cm × 18 cm
Package weight 7.5 kg

 

Maintenance & FAQs

 

Q: Based on test data, how can you determine the quality of a zinc oxide surge arrester?

A:Test data, such as that from a multimeter or test generator, can only provide precise measurements; it cannot indicate whether the device is in good condition. The higher the voltage rating, the greater the leakage current. For the total current fundamental component, values are generally below 0.2 mA for 10 kV–35 kV, around 0.3 mA for 110 kV, around 0.4 mA for 220 kV, and around 0.8 mA for 500 kV. After conducting extensive testing, most customers have developed their own criteria for evaluation.

Q: How to Set the Phase Shift Angle During No-Voltage Measurements

A:The phase‑shift angle setting only works when you run no‑voltage measurements.Our software uses this set angle to calculate resistive current directly - the measured phase angle will be the same as your input value.Because of this, you cannot judge the actual condition of zinc oxide surge arresters by phase‑angle difference under no‑voltage test mode.

Q: How long is the warranty period?

A:1-year warranty + "Three Guarantees" policy.