Battery Discharge Testing Equipment

Battery Discharge Testing Equipment

The HM-300V/150A Battery Discharge Tester discharges battery packs via its integrated electronic load, supporting discharge testing for multi-voltage level packs (10-300V). This tester monitors parameters such as battery voltage, discharge......
Send Inquiry
Description
Technical Parameters

Product Overview & Application Scenarios

-2

The HM-300V/150A Battery Discharge Tester discharges battery packs via its integrated electronic load, supporting discharge testing for multi-voltage level packs (10-300V). This tester monitors parameters such as battery voltage, discharge current, discharge duration, and discharge capacity in real-time during the discharge process. 

 
 

 

 Technical Specifications

 

Model

HM-300V/150A Battery Discharge Tester

Appearance

product-678-895

Weight

Main unit 23(kg)

Dimensions

(mm)

645*263*425mm(WxDxH)

 

 

Testing Procedure Introduction

 

1 Testing Procedure Introduction

Step 1: Connect the single cell modules. (Please note that single cell acquisition modules are optional accessories.)

Step 2: Turn the switch on the tester to the "OFF" position. (To prevent reverse connection of the discharge cable and damage to the instrument).

Step 3: Connect one end of the discharge wire to the tester and the other end to the battery pack. (Note that red is positive and black is negative)

Step 4: Connect the entire set of voltage test leads to the 2-terminal of the battery pack.

Step 5: Connect the tester to the AC220V power supply and close the AC air switch.

Step 6: Plug in the power supply and turn on the tester.

Step 7: Enter the discharge and charge parameter settings.

Step 8: Turn the discharge switch to the "ON" position.

Step 9: Click "OK" to start the test.

HM 300v 150A

Maintenance & FAQs

 

No.

Problem

Solutions

1

The voltage of a single module is all 0.

Check and confirm the wiring method of the wireless module.

2

The voltage of the first three cells of each wireless module is 0.

The wiring sequence is reversed. It should be from No. 0 to No. 6,and start from the positive pole.

3

Module indicator light is off.

The red and black clips of the module require a minimum power of more than 8V.

4

The indicator light of the module flashes slowly, and the module cannot receive data.

The number of modules for the tester is incorrectly filled, and the module location exceeds the range.

5

Buzzer sounds when discharge cable is connected.

The positive and negative connection of the discharge cable is reversed.

6

The discharge current is normal and the voltage does not drop.

The battery pack is not disconnected from the system.

7

Uncontrolled current during discharge.

Please confirm that the internal and external current sensors are selected correctly.

8

Discharge current fault

The air circuit breaker is not closed, the final discharge circuit is not connected, or the battery capacity is too small, and the discharge current is insufficient.

9

Over temperature fault

Confirm the placement of the discharger, pay attention to ventilation and heat flow.

10

After the power is turned on, there is current when the air switch is closed

The discharge circuit may be burnt out and need to be returned to the factory.

11

Data cannot be saved.

Restart the machine, do not switch between internal storage and external storage during the discharge process.

Hot Tags: Battery Discharge Testing Equipment, China Battery Discharge Testing Equipment manufacturers, factory