AC Resonant Test System For 110kV And 220kV GIS Withstand Voltage Testing

AC Resonant Test System For 110kV And 220kV GIS Withstand Voltage Testing

The HMCXZ-2400kVA/600kV Variable Frequency Series Resonant Test System is designed for high-voltage AC withstand voltage testing of GIS, short cables, and power system equipment.
Send Inquiry
Description
Technical Parameters

Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of ac resonant test system for 110kv and 220kv gis withstand voltage testing in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.

 

Products Video

                                 

 

 

Products Description

 

 

 

The HMCXZ-2400kVA/600kV Variable Frequency Series Resonant Test System is designed for high-voltage AC withstand voltage testing of GIS, short cables, and power system equipment.

The system uses a variable frequency power supply to adjust the test frequency and find the resonance point of the test circuit. The control system supports automatic and manual operation, resonance frequency scanning, voltage adjustment, withstand timing, protection, and test data management.

The equipment uses a 7-inch color touchscreen interface based on a 32-bit RISC CPU. The interface displays resonance frequency curves, boost curves, timing curves, and digital feedback of high-voltage voltage, high-voltage current, and low-voltage current.

 

logo3

Variable Frequency Series Resonance Technology

The series resonant test system uses the reactor inductance and test object capacitance to establish a resonant circuit.

The variable frequency power supply adjusts the frequency within the specified range to find the resonance point.

The system's working frequency range is 20–300Hz.

The frequency scanning function allows the starting frequency, ending frequency, and scanning direction to be configured within the specified range.

The resonance tuning process is displayed through the interface, allowing the operator to monitor the resonance curve.

 

Variable Frequency Power Supply Specifications

 

The CHXB-120kW/0.38kV variable frequency power supply is the main frequency adjustment and control component.

Parameter Specification
Model CHXB-120kW/0.38kV
Rated output capacity 120kW
Working power 415V, 50Hz
Output voltage 0–400V
Output type Single-phase
Frequency range 20–300Hz
Rated output current 300A
Output waveform Sine wave
Voltage resolution 0.01kV
Frequency instability ≤0.05%
Voltage instability ≤1.0%
Nonlinear distortion ≤1%
Noise level <50dB
   

 

 

 

 

Main Functions

 

Automatic Frequency Tuning

The control system provides frequency tuning functions for series resonance testing.

Operators can set the start frequency and termination frequency for resonance scanning.

The manual indicates that the frequency range is generally set from 30Hz to 300Hz for resonance finding, while the overall system frequency adjustment range is 20–300Hz.

The system scans the selected frequency range and displays the resonance curve.

When the resonance point is identified, the operator can proceed with voltage boosting and withstand testing.

Control System Functions

The system control interface provides the following functions:

Parameter Setting

Operators can set:

Start frequency

Termination frequency

Tuned voltage

Manual withstand time

Reactor inductance

Test object capacitance

First-stage test voltage

First-stage withstand time

Second-stage test voltage

Second-stage withstand time

Third-stage test voltage

Third-stage withstand time

Alarm voltage

Alarm current

Flashover factor

The system can calculate an approximate resonant frequency after the reactor inductance and test object capacitance are entered.

The manual describes three-stage withstand voltage testing. If a multi-stage test is not required, the operator can select the first stage.

Manual Test

Manual mode allows the operator to:

Start the test system.

Tune the resonance frequency.

Adjust the voltage.

Start the withstand timer.

Stop the test.

Wait until the voltage returns to zero before closing the test interface.

Automatic Test

After the parameters are configured, the automatic mode performs the test process without manual operation of each step.

The operator monitors the equipment status throughout the test.

Test Monitoring and Display

The system interface provides graphical and digital information for test monitoring.

The displayed information includes:

Resonance frequency curve

Voltage boost curve

Timing curve

High-voltage voltage

High-voltage current

Low-voltage current

Resonance frequency

Test object resonance capacitance calculation

These functions allow operators to monitor the test process and view the resonance and voltage adjustment status.

Protection Functions

The system provides protection functions including:

Overvoltage protection

Overcurrent protection

Zero-position start protection

System detuning protection

High-voltage flashover protection

Protection values can be adjusted according to the test requirements.

When flashover occurs, the system activates flashover protection and can record the flashover voltage for analysis.

Test Data Storage and Export

The control system supports test data storage, data query, and report printing.

Test data can be exported through USB.

The manual specifies that the USB should be connected before starting the test when test results need to be uploaded.

The stored data is sorted by testing time, supporting test record identification and retrieval.

 

Applications

 

The variable frequency resonant test system is designed for:

  • AC withstand voltage testing of 110kV GIS
  • AC withstand voltage testing of 220kV GIS
  • Short cable AC withstand voltage testing
  • Power system high-voltage testing

 

FAQ

Q: Can test data be exported?

A: TYes. The system supports USB data export and test report printing.

Q: What information is displayed during testing?

A: The interface displays resonance frequency curves, boost curves, timing curves, high-voltage voltage, high-voltage current, and low-voltage current.

Q: Variable Frequency Resonant Test Equipment Manufacturer

A:Goldhome provides variable frequency series resonant test equipment for AC withstand voltage testing of GIS, short cables, and power system equipment.

The HMCXZ-2400kVA/600kV system integrates frequency tuning, test control, voltage monitoring, protection, and data management functions.

Website: www.hvcablehipot.com

Company  overview

 

01

02

2400kv01

01

04

05

06

07

08

09

 

Hot Tags: ac resonant test system for 110kv and 220kv gis withstand voltage testing, China ac resonant test system for 110kv and 220kv gis withstand voltage testing manufacturers, factory