500A Box Current Injection Test Set

500A Box Current Injection Test Set

Model:HMSLQ 500A Capacity:3kVA Input voltage: single phase 220V±10% / 50Hz±1% Input current: single phase 13.6A
Send Inquiry
Description
Technical Parameters

Product Overview 

 

Product Overview

 Goldhome is committed to innovation, developing the 500A box-type high-current injection for widespread application in power plants, substations, electrical manufacturing plants, research institutes, and other sectors.

 HMSLQ-500A box-type Primary Current Injection is a necessary equipment for high-current field in electrical test, which is used in power plant, distribution substation, electrical equipment manufacturing, scientific research, laboratory and other units. It belong to short or intermittent working system, in small size, light weight, good performance, easy to use and maintenance .

 

Technical Parameter

 

11

Capacity:3kVA

Input voltage: single phase 220V±10% / 50Hz±1%

Input current: single phase 13.6A

Output voltage: single phase 0 ~ 6V (adjustable)/ 50Hz±1%

Output current: single phase 0 ~ 500A

Voltmeter: accuracy /1.0%

Current meter: accuracy 1.0%

The capacity of the equipment is designed according to the 5min short-time working system. If it is used for intermittent work, the power-on time should be less than 2.5min and the working cycle should be more than 10min.

 

Product Description

 

i.panel display:

500a

 

Button Details: 

1 Current Indicator( showing current while step/up or down voltage)
2 Power Indicator(it's on when turn on power switch)
3 Run indicator(it's on after press Start button)
4 Alarm
5 Grounding
6 Power input
7 Connect to tested object
8 Time set
9 Power switch
10 Voltage step down/up
11 Start( press it before step up/down voltage)
12 Times( press it when begin to timing after rise to testing current)
13 Stop

 

II.Product Size

HMSLQ 500A details 2

Product  Cross Weight Package Dimension
Host and Accessory 68kg 590*460*680 L*W*H

 

Working Principle

500a

 

-UK1, 2: Main circuit fuses -FU3, 4: Control circuit fuses
-SP, -ST: Pushbuttons -KM: AC contactor
-HG, -HR: Indicator lamps -T1: Autotransformer
-T2: Low-voltage high-current generator -TA: Current transformer
-S2: Current tap selector switch -S1: Voltage tap selector switch
-PA1, -PA2: Ammeters -PV: Voltmeter

 

Note:

1. This circuit operates on a 220V power supply. When the power supply is 220V, T1 wiring must follow the original company specifications.

2. For currents below 1000A, no voltmeter or S1 switch is required.

3. External copper output wires should be selected at 6A/mm², with a maximum length not exceeding 3 meters.

 

Precautions for Use and Maintenance

 

1. Upon unpacking and inspection, check whether the main circuit terminals are loose and whether the voltage regulator brushes make good contact.

2. When stored for extended periods, use a 500V megohmmeter to check the main circuit's insulation resistance to ground before use. The resistance value should not be less than 0.5 megohms.

3. Input voltage must match the rated value on the nameplate (~220V, ~350V), with a tolerance of -10% to +5%, and a frequency of 50Hz.

4. Do not operate the current tap switch under load.

5. During operation, rotate the handwheel evenly and slowly to prevent damage to the voltage regulator.

6. Continuous operation at full output shall not exceed 5 minutes. Intermittent operation shall be less than 2.5 minutes, with a duty cycle exceeding 10 minutes.

7. The high-current generator housing includes a grounding terminal. Ensure proper grounding during use.

 

Hot Tags: 500A Box Current Injection Test Set, China 500A Box Current Injection Test Set manufacturers, factory, meter current injection test set, DC Primary Current Injection Test Set, relay current injection test set, manual current injection test set, portable current injection test set, generator current injection test set