The HMSLQ 7000A High-Current Injection Test System is essential equipment for electrical commissioning applications requiring high currents across various industries. It is widely used in power plants, substations, electrical equipment manufacturing plants, research institutions, and laboratories. This system is designed for short-term or intermittent operation, but it can also operate continuously for extended periods (≤24 hours at full load).
Send Inquiry
Description
Technical Parameters

Product Overview & Video

 

7000A 12V Long Time Running Primary Current Injection Test Display Video

 

 

Products Description

 

 

7000A01

The HMSLQ 7000A High-Current Injection Test System is essential equipment for electrical commissioning applications requiring high currents across various industries. It is widely used in power plants, substations, electrical equipment manufacturing plants, research institutions, and laboratories. This system is designed for short-term or intermittent operation, but it can also operate continuously for extended periods (≤24 hours at full load).

 

Technical Specifications

 

Induction Voltage Regulator (Three Units Integrated into One) Input Voltage 380V / Single-phase (per unit)

Rated Capacity 50kVA × 3

Input Current 131.5A

Output Voltage 25–650V

Output Current 76.9A

Operating Time ≤24 hours

Cooling Method Oil circulation cooling

Electric Control Console Input Voltage 380V / Three-phase

Input Current 227.9A

Rated Capacity 150kVA

Output Current Indication 7000A (three-phase indication)

Output Voltage Indication 450V

Instrument Accuracy Class 0.5

Overcurrent Setting Range 100–7000 A (configurable for three-phase or single-phase)

Current Balancing Function Adjustable for each phase or individually for single-phase; intelligently and automatically balances three-phase output

Overcurrent Bounce Release Time 7 ms

Timing Range 0–999 seconds/minutes/hours (switchable)

Operating Time ≤24 hours

Cooling Method Forced air cooling

Primary Current Generator (Boost Transformer) Input Voltage 0–600 V / Three-phase (combination of three single-phase units)

Input Current 0–80.5 A

Rated Capacity 48.3 kVA × 3

Output Voltage Phase voltage 0.46–12 V, line voltage 0.26–6.9 V (open circuit)

Output Current 100–7000 A

Current Transformers HL1-10000A/5A (3 units), Class 0.5 accuracy

Operating Time ≤24 hours

Cooling Method Forced air cooling with fans

 

 

Maintenance & FAQs

 

Q: Does the device have three-phase or single-phase output?

A: The device supports both three-phase and single-phase output modes, and the output current can be adjusted freely between three-phase and single-phase.

Q: Is the device complicated to operate? Does it require professional training?

A: It is not complicated; ordinary technicians can operate it after a brief training session.

Q: What is the difference between automatic and manual modes?

A: What is the difference between automatic and manual modes?

 