Products Description

The HMSLQ-3000A/50V DC High-Current Generator consists of a rectifier transformer and a rectifier unit. It employs a 6-pulse thyristor (SCR) rectifier circuit and achieves continuous adjustment of DC current and voltage through phase-shift voltage regulation. The system features constant-voltage and constant-current control functions. The main controller utilizes our company's latest dedicated trigger board, ensuring high control precision and excellent symmetry between positive and negative pulses. The equipment offers comprehensive protection functions, strong interference resistance, high reliability, simple operation, and a high degree of automation, and complies with IEC international standards and relevant industry standards.
System Parameter
- Model HMSLQ-3000A/50V
- AC Input Voltage 400 VAC ±10%, 50 Hz ±1 Hz or 480 VAC ±10%, 60 Hz ±1 Hz (three-phase, four-wire)
- DC Output Voltage 0–50 VDC (continuously adjustable)
- DC Output Current 0–3000 A (continuously adjustable)
- Maximum DC Output Power 150 kW
- Constant Current/Constant Voltage Control Accuracy ≤±1.2%
- DC Ripple Coefficient ≤4% (at rated output)
- Source Effect ±0.3% (grid voltage fluctuation from -10% to +10%)
- Load Effect ±0.5% (load fluctuation from -10% to +10%)
- Overall Efficiency ≥88% (typical value 90%)
- Trigger Pulse Asymmetry ≤1°
- Current Regulation Method Continuous, stepless adjustment
- Cooling Method Forced air cooling
- Duty Cycle Continuous (can operate continuously at full load)
- Load Class Class I
- Thyristor Temperature Monitoring 6 thermocouples (A+, A-, B+, B-, C+, C-)
- Protection Functions Overcurrent, overvoltage, overtemperature, emergency stop
- Data Storage 100 sets of test records; supports export to USB flash drive and printing
- Operating Environment Indoor, -20°C to +40°C, relative humidity 15% to 85%, altitude < 1,500 meters
- Vibration Resistance Horizontal 0.2g, Vertical 0.1g
- Insulation Resistance (after prolonged inactivity) ≥2 MΩ (500 V megohmmeter)

features & Functions
- Wide Voltage Input Range: Supports 400 VAC ±10% (50 Hz) or 480 VAC ±10% (60 Hz)
- High-Quality Components: Features premium low-dropout components, with overall efficiency as high as 90%
- Comprehensive Protection Features:
- Overcurrent Protection (configurable output current limit)
- Overvoltage protection (configurable upper output voltage limit)
- Thyristor overheat protection (real-time monitoring via 6 thermocouples; alarm and shutdown upon overheating)
- Emergency stop (E-Stop)
- Constant current/constant voltage control: Accuracy ≤±1.2%
- Low ripple: DC ripple coefficient ≤4% (at rated output)
- Dual-closed-loop regulation: Trigger pulse asymmetry ≤1°, stepless phase shift adjustment
- High-capacity design: Maximum DC output power 150 kW
- Long-Term Continuous Operation: Capable of sustained operation at 3000 A/50 V rated output for extended periods
- Human-Machine Interface: Touchscreen operation; supports both manual and automatic test modes; allows setting of parameters such as current rise/fall rates, target current, hold time, and alarm thresholds
- Data Management: Stores up to 100 sets of test data; supports export to USB flash drive and printing
Products Details




Hot Tags: dc primary current injection test system, China dc primary current injection test system manufacturers, factory