Comprehensive Voltage-Current Characteristic Tester

Comprehensive Voltage-Current Characteristic Tester

The HM6060B is a fully automatic, all-in-one testing instrument developed by Goldhome, specifically designed for protective and metering CTs/PTs. It can perform a full range of tests, including voltage-current characteristics, turns ratio, polarity, error curves, primary current injection, and AC withstand voltage, meeting the needs of both laboratory calibration and portable on-site testing.
Send Inquiry
Description
Technical Parameters

Products video

HM6060B Comprehensive Voltage-Current Characteristic Tester Display Video

 

Product Overview

 

HM6060B03

HM6060B Transformer Voltage-Current Characteristic Tester, a fully automatic CT/PT comprehensive tester that measures voltage-current characteristics, turns ratio, polarity, inflection points, and secondary resistance/load. This single unit replaces traditional voltage boosters, current boosters, and meters.

 

 

Products parameters

 

Item Parameter
Power Supply AC220V±10% ,50Hz
Device Output 0~1000V(20 A peak)
注:0–5A are actual values; values greater than 5A up to 20A are calculated values
High-Current Output 0~600A
Excitation Measurement Accuracy ≤0.5% (0.2% × reading + 0.3% × range)
CT
Turns Ratio Measurement
Range ≤5000A/1A(25000A/5A)
  Accuracy ≤0.5%
PT
Ratio Measurement
Range ≤500KV
  Accuracy ≤0.5%
Operating Environment Temperature: –10°C to 40°C, Humidity: ≤90%, Altitude: ≤1000 m
Dimensions and Weight Dimensions: 410 mm × 260 mm × 340 mm, Weight: ≤22 kg

 

Operation Methods and Main Interface Overview

 

1. How to Use the Controller

The controller has three operating modes: "Rotate Left," "Rotate Right," and "Press." These three functions allow you to easily move the cursor, enter data, and select items.

2. Main Menu (See Figure 2)

The main menu contains seven options: "Excitation," "Rating Ratio and Polarity," "AC Withstand Voltage," "Primary Current Injection," "Data Query," "Demagnetization," and "Back." These can be selected and configured using the controller.

 

 

HM6060B                                     HM6060B 1

 

product-46-13Figure 2, CT Main Interface                                                                                                            Figure 3, PT Main Interface

 

 

 

8. CT Testing

To perform tests on the current transformer's excitation characteristics, turns ratio, polarity, primary current, AC withstand voltage, and demagnetization, move the cursor to "CT" and select the corresponding test option.

1. CT Excitation (V-A) Characteristic Test

Press the "Excitation" button to enter the test interface, as shown in Figure 4.

1) Parameter Settings:

Excitation Current: The setting range (0–20 A) represents the maximum current the instrument can output. If the current reaches the set value during the test, the current increase will automatically stop to prevent equipment damage. Typically, a current setting of 1 A or higher is sufficient to detect the inflection point.

Excitation Voltage: The setting range (0–1000 V) represents the maximum voltage the instrument can output. Typically, the voltage should be set slightly higher than the inflection point voltage to ensure a more balanced curve display. If the voltage is set too high, the curve will approach the Y-axis; if set too low, it will approach the X-axis. If the voltage reaches the set value during the test, the instrument will automatically stop increasing the voltage to prevent equipment damage.

 