150kV SF6 PD Free HV Test Transformer

150kV SF6 PD Free HV Test Transformer

GOLDHOME HM-YDQW-20/150 Partial Discharge-Free Test Transformer System, with a rated capacity of 20 kVA and a high voltage of 150 kV, features a partial discharge level of less than 5 pC at 100% UH. It is suitable for power-frequency withstand voltage testing of insulation materials and electrical products.
Send Inquiry
Description
Technical Parameters

Products Description

 

 

 

1

 

GOLDHOME HM-YDQW-20/150 Partial Discharge-Free Test Transformer System, with a rated capacity of 20 kVA and a high voltage of 150 kV, features a partial discharge level of less than 5 pC at 100% UH. It is suitable for power-frequency withstand voltage testing of insulation materials and electrical products.

 

 

 

 

product features

 

  • Power-Frequency Partial Discharge-Free Test Transformer (HM-YDQW-20/150)
  • Structure Type: Vertical, Metal Enclosure
  • Number of Phases: Single-phase
  • Frequency: 50 Hz
  • Rated Capacity: 20 kVA
  • Input Voltage: 0.4 kV
  • Input Current: 50 A
  • High-Voltage Winding: 150 kV
  • High-Voltage Current: 0.13 A
  • Waveform Distortion Rate: ≤3%
  • Measuring Winding Voltage Ratio: 1500:1
  • Overcurrent Capacity: Under operating conditions of 150% In (rated current) for 300 seconds, the overcurrent shall not cause thermal damage or deformation to the test transformer windings.
  • Overvoltage Capacity: Under an overvoltage condition of 110% UH (165 kV) for 60 s, no insulation damage to the test transformer shall occur, and the waveform distortion rate shall be ≤5% during this period.
  • Insulation Level: Power-frequency withstand voltage level of 5 kV/1 min between the low-voltage input terminals and ground
  • Dielectric Loss: <0.3%
  • Noise: ≤60 dB
  • Electrical Strength of Insulating Medium: Breakdown voltage greater than 5 kV/2.5 mm; trace moisture content less than 10 ppm; dielectric loss factor less than 0.3% (at 90°C)
  • Partial Discharge Level: Less than 5 pC at 100% UH; less than 3 pC at 80% UH
  • Voltage Non-uniformity: ≤±5%
  • Operating Time: Permitted to operate for 10 minutes starting from ambient temperature at 100% UH and IH; permitted for continuous operation starting from ambient temperature at 80% UH and IH, with transformer winding temperature rise ≤ 65 K.

2

 

 

fAQ

Q: What is the partial discharge level of this system?

A: At 100% of the rated voltage (150 kV), the system's partial discharge level is less than 5 pC; at 80% of the rated voltage, it is less than 3 pC.

 

Q: Is the system gas-insulated or oil-immersed?

A: It features a gas-insulated (SF6 gas insulation) design, offering advantages such as compact size, light weight, no oil contamination, and maintenance-free operation.

 

Q: Does the system support automatic operation?

A: Yes. It is equipped with an intelligent control system that features automatic voltage ramp-up and ramp-down test functions. The voltage ramp-up rate is configurable, and the system automatically starts timing once the set voltage is reached.

 

Products Details

01

02

03

04

 

 

 