600kV AC Variable Frequency Resonant Test System (2400 KVA, 600 KV)

600kV AC Variable Frequency Resonant Test System (2400 KVA, 600 KV)

The HMCXZ-2400kVA/600kV is designed and manufactured for AC withstand voltage testing of 110 kV and 220 kV GIS, short cable runs and power system equipment. It is the type of set bought by local, municipal and county-level high-voltage test departments, and by power installation and repair engineering units that need to prove insulation on site rather than send the specimen to a laboratory.
Send Inquiry
Description
Technical Parameters

Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of 600kv ac variable frequency resonant test system (2400 kva, 600 kv) in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.

 

Products Video

                                 

 

 

Products Descriptions

logo5

The HMCXZ-2400kVA/600kV is designed and manufactured for AC withstand voltage testing of 110 kV and 220 kV GIS, short cable runs and power system equipment. It is the type of set bought by local, municipal and county-level high-voltage test departments, and by power installation and repair engineering units that need to prove insulation on site rather than send the specimen to a laboratory.

The set is four units working as one circuit: a variable frequency control power supply (CHXB-120kW/0.38kV), an excitation transformer of 120 kVA with 5 kV, 10 kV and 20 kV outputs, two oil-immersed high-voltage reactors of 1200 kVA / 300 kV / 4 A, and a 600 kV capacitive divider of 1000 pF. The reactors are built as separate units rather than one block, which is what allows the same set to serve both high-voltage, low-current specimens and the lower-voltage, higher-current ones.

Because the circuit is tuned to series resonance with the specimen, the supply only has to cover the active losses. The document states the power required for the test is 1/Q of the test capacity, and the device quality factor is 30 or more at 45 Hz - which is how a 120 kW power supply, an excitation transformer and two reactors produce a 2400 kVA rating at the specimen without a 2400 kVA mains connection.

Control is a 7-inch true-colour touch screen built on a 32-bit RISC CPU, showing the resonance frequency curve, the boost curve and the timing curve, with high-voltage current, high-voltage voltage and low-voltage current fed back as true RMS values. The system also calculates the resonant frequency from the entered inductance and capacitance, and reports the specimen's resonant capacitance.

 

Key features

 

 
 
 

2400 kVA from a 120 kW supply

Series resonance means the supply delivers only the active losses; the power needed is 1/Q of the test capacity. 

 
 

Two reactors, two voltage classes

Two 1200 kVA / 300 kV / 4 A reactors give 600 kV at 4 A in series and 300 kV at 8 A in parallel, with 2400 kVA in both.

 
 

20–300 Hz working band

The supply adjusts from 20 to 300 Hz with frequency instability of 0.05% or less, so the resonance point is found by frequency rather than by tap.

 
 

Clean output waveform

Output voltage distortion is 1% or less; the resonant circuit acts as a filter, which the document credits with preventing harmonic peaks from breaking down the specimen..

 
 

Protected at breakdown

Over-current, over-voltage and specimen-flashover protection, with adjustable over-voltage and over-current settings and the flashover voltage recorded for analysis.

 
 

Three-stage withstand program

Each stage takes its own test voltage and withstand time; a single stage is used for cable work, where only a stable output is required.

 
 

Automatic and manual modes

Automatic runs the sequence unattended; manual gives Tune, voltage step up and down, and Timing, for specimens that need watching.

 
 

Records and reports

Results stored under the testing time as the record number, printable from the controller and exportable over USB for review on a computer.  

Specifications

 

System

Parameter Value
Rated capacity 2400 kVA
Rated voltage 300 kV / 600 kV
Rated current 8 A / 4 A
Input power supply Three-phase 380 V, 50 Hz
Working frequency 20–300 Hz
Output waveform distortion ≤1%
Duration Continuous 60 min at rated load, then 60 min rest
Temperature rise at rated load ≤65 K
Quality factor Device Q ≥30 at f = 45 Hz
Measurement accuracy System RMS class 1.5
Protection Over-current, over-voltage, specimen flashover

 

Variable frequency power supply - CHXB-120kW/0.38kV

Parameter Value
Rated output capacity 120 kW
Working power 415 V, 50 Hz
Output voltage 0–400 V, single phase, 20–300 Hz
Rated output current 300 A
Output waveform Sine wave
Voltage resolution 0.01 kV
Frequency adjustment range 20–300 Hz
Frequency instability ≤0.05%
Voltage instability ≤1.0%
Nonlinear distortion ≤1%
Running time Continuous 60 min at rated capacity
Component temperature ≤65 K after 60 min at rated capacity
Noise level Less than 50 dB
Panel controls Print Power, E-Stop, Reset, Power Indicator

The USB drive must be connected to the control box before power is switched on, otherwise the test result cannot be uploaded.

 

Excitation transformer - 120kVA/5kV/10kV/20kV/0.4kV

Parameter Value
Rated capacity 120 kVA
Input voltage 400 V, single phase
Output voltage 5 kV / 10 kV / 20 kV
Structure Oil type
Duty time Continuous 60 min at rated current
Terminals 400 V input, HV tail / grounding, 5 kV, 10 kV, 20 kV outputs

The 5 kV, 10 kV and 20 kV terminals are selected according to the test requirement; the HV tail must be grounded in good condition.

 

High voltage reactor - DK-1200kVA/300kV (2 pcs)

Parameter Value
Rated capacity per unit 1200 kVA
Rated voltage 300 kV
Rated current 4 A
Inductance 300 H per unit
Quality factor Q more than 50 at f = 45 Hz
Structure Oil type
Duty time Continuous 60 min at rated current
Terminals Input on the base, output on the top

 

Capacitor voltage divider - FCR-600kV/1000pF

Parameter Value
Rated voltage 600 kV
High-voltage capacitance 1000 pF
Dielectric loss tgσ less than 0.15%
Measuring accuracy 1.5
Ratio, console 2608034-1 1 section 26282:1 / 2 sections 13141:1
Ratio, console 2608034-2 1 section 26428:1 / 2 sections 13214:1
Grounding Two terminals - the divider itself and its base

 

Working environment and safety

Parameter Value
Ambient temperature −15 to 45 °C
Relative humidity ≤90% RH
Altitude ≤2500 m
Grounding resistance Less than 2 Ω; a higher value may damage the system
Reactor siting Not on metal or metal-mesh prefabricated ground
Operators Qualified high-voltage test personnel, no fewer than two

 

FAQ

Q: Are test results stored and printable?

A:Yes. Data is stored under the testing time as the record number, printable from the controller after pressing Print Power, and exportable over USB. The USB drive must be inserted before the test starts, otherwise the result cannot be uploaded.

Q: What working environment and earthing does it need?

A: Ambient temperature from minus 15 to 45 degrees Celsius, relative humidity up to 90% RH and altitude up to 2500 metres. The grounding resistance must be less than 2 ohms; a higher value may damage the series resonance test system.

Q: How long can the system run at rated load?

A:Continuously for 60 minutes at rated load, followed by 60 minutes of rest. The temperature rise at rated load is no more than 65 K.