Products overview & Applications

The HMCXZ 216kVA 216kV system consists of a 10kW variable-frequency power supply, a 10kVA three-tap excitation transformer, six DK-36kVA/36kV dry-type reactors, a 220kV capacitive voltage divider, insulating supports, and a complete set of supporting wiring.
Application: 30–300 Hz variable-frequency AC withstand voltage testing. By combining reactors in series or parallel configurations, this system can perform power frequency and variable-frequency withstand voltage tests on electrical equipment such as high-voltage cables, transformers, GIS, switches, current transformers, and insulators.
features
- Flexible Reactor Configuration: Six independent single-section reactors that can be freely combined in series or parallel to accommodate test specimens with varying voltages and capacities; comes with dedicated insulated mounting brackets.
- Excellent Electrical Performance: Q ≥ 36 for a single reactor; Q = 54 in series configuration; low noise (30–35 dB); inductance error controlled within ±5%.
- Multi-Voltage Excitation: Three output voltage settings (3 kV, 6 kV, 9 kV) to accommodate various reactor configurations and test voltage scenarios.
- Comprehensive Protection: The variable-frequency power supply integrates overvoltage, overcurrent, emergency shutdown, and fault reset protection.
- Full Factory Testing: Comprehensive factory inspection covering appearance, structure, insulation resistance, DC resistance, power frequency withstand voltage, and resonance performance; the unit is released only after passing all tests.
Products indication
- Rated Total Capacity: 216 kVA
- Rated Voltage: 216 kV
- Rated Total Current: 1 A
- Rated Frequency: 30–300 Hz
- Inductance of Fixed Reactors: 120 H each
- Excitation Transformer JLB-10kVA/3kV/6kV/9kV/0.4kV
- Rated capacity 10kVA, input 400V/25A, output 3/6/9kV, output current 3.3/1.7/1.1A
- Frequency Converter CHXB-10kW/220V/380V
- Rated capacity 10 kW, input 380 V/220 V, output 0–400 V/0–25 A, frequency 30–300 Hz
- High-Voltage Reactors (6 units) DK-36kVA/36kV
- Rated capacity 36 kVA, rated voltage 36 kV, rated current 1 A, inductance 120 H ±5%
- Capacitive Voltage Divider FRC-220 kV/750 pF
- Rated voltage 220 kV, capacitance 750 pF, accuracy class 1.5

Hot Tags: ac series resonant test set for transformer, China ac series resonant test set for transformer manufacturers, factory