Product Overview & Application Scenarios
Product Overview
HM6080 Circuit Breaker Analyzer is a special instrument which development and manufacture by our company for various high voltage switching action characteristic test, it can measure accurately the mechanical dynamic characteristic parameters of low oil,high oil,vacuum,SF6 and so on high voltage circuit breaker with various voltage classes.the instrument adopted large screen display,English hints man-machine conversation mode,English display results and print out, has advantages of intelligentize, multi-functional,accurate data,strong anti-interference,easy operation,small size,light weight,nice appearance.
Key Features & Advantages
1.Suitable for all model SF6 switch,GiS composite apparatus,vacuum switch,oil switch's mechanical characteristic test.
2.Excellent anti-interference ability,even under condition of near the 500KV transformer substation bypass bus bar is charged,it can finish test easily and output accurate results.
3.Large screen,HP series,direct perspective,background light liquid crystal,all English display all data and diagram,electric adjustment of liquid crystal contrast,power off memory.
4.English menu operation,easy to use,the instrument has built-in printer,print out all data and diagram at any time.
Additional Information
1. Environmental Conditions
Operating Temperature: -10°C to +50°C (14°F to 122°F)
Storage Temperature: -20°C to +70°C (-4°F to 158°F)
Relative Humidity: < 80% (Non-condensing)
Altitude: < 2000 meters (6560 feet)+
2. Electrical & Safety Conditions
Power Supply:
Internal Battery: Typically a rechargeable Li-ion battery pack.
External Charger/Adapter: As specified by the manufacturer (e.g., 100-240V AC, 50/60Hz). Only use the provided charger.
Earthing (Grounding): The analyzer and the circuit breaker under test MUST be properly grounded.
3. Physical & Usage Conditions
Ingress Protection (IP): Typically IP20 or similar for the main unit.
Mechanical Stress: Protect the instrument from severe shock, vibration, and strong magnetic or electric fields.
Positioning: Ensure the instrument is placed on a stable, flat surface during operation to prevent it from falling. The test leads and cables should be routed neatly to avoid tripping hazards.
Maintenance & FAQs
Q: Why are my timing readings unstable or incorrect?
A: Common causes include:
Loose Connections: Ensure all test leads and sensors are securely connected.
Sensor Issues: The travel sensor may be slipping or not properly aligned.
Incorrect Settings: Verify the number of poles, expected times, and trigger settings in the software.
Low Battery: A low battery can cause erratic behavior.
Hot Tags: hv circuit breaker tester, China hv circuit breaker tester manufacturers, factory
Technical Specifications
Technical parameters
Operating environment
Input power supply: 220V±10% 50Hz±10%
Atmospheric pressure: 86~106kPa
Temperature: -10~40℃
Humidity: ≤80%RH
Safety performance
Dielectric strength: Power on power frequency 1.5KV pressure for 1 minutes.,without any arc over.
Basic parameters
Time: Measurement range: 4000.0ms
Time:Resolution: 0.1ms
Error: Within 100ms 0.1ms±1 words
Above 100ms 0.1%±1 words
Synchronization ±0.1ms
Speed: Measurement range: 20.00m/s Speed: Resolution: 0.01m/s
Error: Within 0-2m/s ±0.1m/s±1 words
Above 2m/s ±0.2m/s±1 words
Travel:
|
|
Measurement range |
Resolution |
Error |
|
Vacuum circuit breaker |
50.0mm |
0.1mm |
1%±1 digit |
|
SF6 Circuit breaker |
300.0mm |
1mm |
|
|
Oil-minimum breaker |
600.0mm |