Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of high voltage partial discharge shielding room in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.
Product Overview & Application Scenarios
Overview:
Goldhome has rich experience and mature technical support in high voltage partial discharge shielding rooms, providing high-quality products and reasonable prices.
High Voltage Partial DIscharge for Test Shielded Room is a precision testing facility designed to detect partial discharge (PD) phenomena in high - voltage electrical equipment. By capturing high - frequency signals, it ensures accurate monitoring. Comprising a detection system and a shielding system, it integrates electromagnetic shielding, insulation protection, and signal amplification functions, guaranteeing both safety during testing and data reliability.
⚫ Test Subjects: Switchgear, voltage and current transformers, organic composite insulators, cables, generators, etc;
⚫ Test Items: Support for partial discharge testing;
⚫ Compliance Standards: GB12190-2006 Measurement Methods for Shielding Effectiveness of Electromagnetic Shielding Rooms.
Operating Conditions
- Altitude: 1000m;
- Ambient Temperature: -5°C to 45°C;
- Relative Humidity: 90% (non-condensing);
- Installation Location: Indoor;
- Seismic Resistance: 8 on the seismic intensity scale;
- Ground Resistance: 19 ohms;
- Operating Environment: Free from conductive dust, gases, or liquids that corrode insulating materials or metal surfaces.
Equipment Features

1. The shielded room floor employs a new construction method requiring no excavation or internal concrete pouring. The interior floor is only approximately 2 cm higher than the exterior, ensuring unimpeded access for personnel and forklifts.
2. A combination of modular assembly and welding facilitates relocation and disassembly while maintaining shielding performance.
3. Exterior walls are clad with premium tongue-and-groove sandwich panels made of fire-resistant and flame-retardant materials, adding an aesthetically pleasing decorative layer;
4. Control room flooring utilizes high-quality composite flooring for a premium, sophisticated appearance.
Key Technical Parameters
Electric Field Attenuation: 1kHz~1GHz ≥60dB
Magnetic Field Attenuation: 10kHz~5MHz ≥60dB
Plane Wave Attenuation: 50MHz~10GHz ≥60dB
Grounding system: <1Ω
System background: ≤12pC
Insulation of isolation layer: >1000MΩ
(measured in excavated shielded rooms; not measured in non-excavated shielded rooms)

Layout Diagram
The shielded room layout is for reference only; the actual layout and dimensions shall be subject to on-site survey.

Maintenance FAQs
Optimized for Google promotion with SEO - friendly keywords, clear technical terms, and concise formatting.
Hot Tags: High Voltage Partial Discharge Shielding Room, China High Voltage Partial Discharge Shielding Room manufacturers, factory, energy audits of partial discharge test sets