Product Overview
Overview:
Due to SF6 gas's excellent insulation properties, arc-quenching capabilities, and non-flammability, it has gained widespread application as a new insulating medium. After years of dedicated research, Goldhome Hipot has successfully developed a gas-insulated SF6 power GIS fault simulation device. Leveraging the superior insulation and arc - quenching properties of SF6 gas, this device integrates a high - voltage partial - discharge - free system to accurately simulate multiple fault types, including corona discharge, floating discharge, void discharge, particle discharge, and surface discharge. It supports composite discharge mode generation, making it a core tool for power research, education, and instrument calibration
product Features

1. Compact design for minimal space requirements
2. Lightweight components
3. Rugged construction withstanding long-distance transportation
4. Capable of performing various tests in unshielded environments
5. All high-voltage sections enclosed in sealed compartments for operator safety
6. Wide application range; can conduct withstand voltage tests on conventional equipment with additional bushings.
7. Integrated high-voltage measurement and partial discharge coupling capacitor.
8. System-wide partial discharge level below 1 pC, guaranteeing test data accuracy.
Products Parameter
|
Parameter |
Technical Specifications |
|
Rated Voltage |
0–100kV (adjustable) |
|
Partial Discharge Level |
≤1pC |
|
Discharge Simulation Range |
Corona: 5–800pC; Particle: 0.1–10pC; Floating: 100–20,000pC; Void / Surface: 10–1,000pC |
|
Coupling Capacitance |
100pF / 50pF (subject to actual configuration) |
|
Power Supply |
220V AC / DC ±10%, 22.7A |
|
SF6 Gas Pressure |
0.4MPa (factory default); Annual leakage ≤1% |
|
Protection Class |
IP32 |
|
Operating Temperature |
10°C–50°C (indoor / outdoor) |
Product Introduction

Control Panel Layout Diagram
| 1-Power Socket | 2-Digital Time Relay |
| 3-Electronic Current Adjuster | 4-Start, Stop, Timing Buttons |
| 5-High-Voltage Indicator Gauge | 6-Low-Voltage Current Indicator |
| 7-Signal Lamp, Alarm Flashing Light | 8-Terminal B Block |