Vacuum Interrupter Tester

Vacuum Interrupter Tester

The HM6070 is a non-disassembly vacuum tester designed for vacuum circuit breakers. Utilizing magnetron discharge technology, it measures vacuum levels without the need to remove the vacuum flask. This device is widely used for on-site testing of 10 kV and 35 kV vacuum circuit breakers, switches, and circuit breakers.
Send Inquiry
Description
Technical Parameters

Products video

 

HM6070 Vacuum Circuit Breaker Tester Test Introduction Video

 

 

 

                                                                           

Product Overview 

 

HM607003

The HM6070 is a non-disassembly vacuum tester designed for vacuum circuit breakers. Utilizing magnetron discharge technology, it measures vacuum levels without the need to remove the vacuum flask. This device is widely used for on-site testing of 10 kV and 35 kV vacuum circuit breakers, switches, and circuit breakers.

Products features

 

  • Non-disassembly testing: The magnetron coil is mounted directly on the exterior of the arc-extinguishing chamber, eliminating the need to remove the vacuum bulb and enabling rapid on-site testing.
  • Fully automatic measurement: One-button startup automatically completes pressurization, sampling, calculation, and display, taking approximately 20–40 seconds per test.
  • Wide range and high precision: Covers 10⁻⁵ to 10⁻¹ Pa, meeting power industry preventive testing standards.
  • Portable and durable: The main unit weighs 24 kg, making it suitable for on-site use at substations, power plants, and industrial and mining enterprises.
  • Data management: Supports data storage, USB export, and printing, meeting testing documentation requirements.

HM607002

Products Description

 

HM607004

  • Detection objects: various models of vacuum switch
  • Detection method: using new excitation coil and detect vacuum tube without disassembly
  • Application area: This instrument is a all-purpose type, can measure the vacuum of variety models of open magnetic vacuum tube.
  • Detection range: 10-5-10-1 Pa
  • Measurement accuracy: 10-5-10-4 Pa, 15%
  • 10-4-10-3 Pa, 15%
  • 10-3-10-2 Pa, 10%
  • 10-2-10-1 Pa, 10%
  • Magnetic field voltage: 1700V
  • High-voltage of pulsed electric field: 30KV
  • Open distance of switch tube in vacuum test: normal open distance
  • Testing environment: -20℃~ 40℃
  • Weight: 24kg
  • Dimension: 420 × 320 × 280 (mm)
  • Sampler: magnetic coil

 

 

Operation Steps

 

Instrument Panel and Wiring Instructions

HM6070

 

 

product Details

HM6070 details 3

HM6070 details 1

HM6070 details 4

HM6070 details 2

HM6070 details 5-similar product

 

Hot Tags: vacuum interrupter tester, China vacuum interrupter tester manufacturers, factory