Vacuum Oil Transformer Filter

Vacuum Oil Transformer Filter

The ZYD Series High-Efficiency Two-Stage Vacuum Oil Purifier is a specialized device designed for the deep purification of insulating oil used in transformers and other equipment. By integrating multiple technologies, this equipment efficiently removes moisture, gases, and impurities from oil.......
Send Inquiry
Description
Technical Parameters

Products Video

 

 

ZYD Seires 2 Stage Vacuum Oil Filter Display Video

Product Overview & Applications

 

111

The ZYD series oil purifier efficiently removes moisture, gases, and impurities from insulating oil, enhancing its dielectric strength to ensure the safe operation of electrical equipment. Primarily used in power utilities and industrial enterprises, it treats substandard transformer oil, instrument transformer oil, switchgear oil, and similar fluids.

Control panel operating procedures

 

222

1.The external wiring of the control panel is shown in the electrical wiring diagram. Connect the 380V three-phase fourire AC power from the lower left hole of the electrical control cabinet, and ensure the control panel is reliably grounded.

2.Close the main power switch, the power light on the control panel will light up, indicating the power is connected.

3.During heating, turn on the temperature controller switch; the red light being on it is in the preparation state. Then, set the temperature control knob to the working temperature to start heating the oil. When the oil temperature reaches the set, the temperature controller will automatically turn off the heater. Therefore, it has the functions of automatic heating and constant temperature control.

4. After stopping the operation, the main power switch, and then lock the electrical control cabinet door.

 

 

Products diagram

 

 

ZYD

 

ZYD 2

 

Maintenance & FAQs

 

Q: : The vacuum degree decreases?

A:

1.Refer to the vacuum pump manual.

2. Inspect and repair the piping.

3. Refill the vacuum pump oil to the oil mark.

4. Replace with new oil.

5. This is a normal phenomenon. Calibrate or replace

Q: Oil enters the vacuum pump?

A:

1.Properly control the oil intake to maintain the oil level at the middle position of the liquid level gauge.

2.Reduce the vacuum degree.

3. The oil in the vacuum pump should be drained, the vacuum pump should be cleaned, and the vacuum pump oil should be replaced. When working again, the oil quantity to achieve a balance between the oil intake and output.

Q: Water enters the vacuum pump?

A:

1. Observe the liquid level gauge in the cooler. If the water level is high,

2. The vacuum pump should be drained and cleaned and the vacuum pump oil should be replaced.

Q: Vacuum pump - motor stops during operation?

A:

1. Suspend use

2. Check the power supply

Q:Reduced oil discharge?

A:

1. Increase the oil intake

2. Decrease the vacuum

3. Lower the height

4. Change oil seal

 