Automatic Transformer Test Bench

Automatic Transformer Test Bench

Brand Name:HMDQ; Model:HM5050; Product name:Transformer Test Bench; Size:wide×height×depth (400×174×479)mm or wide×height×depth (387×132×360)mm
Send Inquiry
Description
Technical Parameters

Products Video

 

HM5050 TransformerI Integrated Comprehensive Test Bench Display Video

 

Product Parameter

 

 

111

 Standard Current Transformer

 500/5 standard current transformer 3pcs

 Rated voltage:3kV

 Rated primary current:500A

 Rated secondary current:5A

 Measurement accuracy:0.2%

  250/5 standard current transformer 3pcs

 Rated voltage:3kV

 Rated primary current:250A

 Rated secondary current:5A

 Measurement accuracy:0.2%

Parameters

Measuring Range

Measurement Error

Voltage

500V

±(0.25%Rx+0.25%RA)

Current

5A

±(0.25%Rx+0.25%RA)

Active power

U×I

±(0.25%Rx+0.25%RA)

Power factor

0.010~1.000

±0.03

Frequency

(40~300)Hz

±0.5%

Working power supply

AC220V±22V,50Hz±1Hz

Overall Power Consumption:

Less than 15VA

Ambient temperature

(0~40)℃

Relative humidity

30%~90%

Size

wide×height×depth (400×174×479)mm

or wide×height×depth (387×132×360)mm

Weight

< 5kg

 

Product Description

 

1.No-load/load loss Test and Temperature Rise Test

 

HM505001

Figure1.Parameter Set  

1.1 "Test Current": It means the average current input to the tested object. While choose test voltage "500V/5A", test current 0~5A freely adjustable ; While choose test voltage "500V",test current 0~500A freely adjustable ; While choose voltage 1000V,test current 0~300A freely adjustable;While choose test voltage 2000V, test current 0~200A freely adjustable;While choose test voltage 3000V, test current 0~100A freely adjustable.

1.2 "Alarm Current": While choose test voltage 500V/5A, set alarm current 0~6A freely adjustable, While choose test voltage is 500V, set alarm current 0~550A freely adjustable.

While choose test voltage 1000V,set alarm current 0~350A freely adjustable;

While choose test voltage 2000V,set alarm current 0~250A freely adjustable;

While choose test voltage 3000V, set alarm current 0~150A freely adjustable .

1.3 "Manual Keep Time": It means current withstand time in Manual mode .

1.4 "Auto Keep Time": It means current withstand time in Auto mode

1.5 "Choose Test Voltage (Mandatory)": Choose test voltage according to tested object .

1.6 "Auto": Click it into Auto test interface

1.7 "Manual": Click it to enter into Manual test interface .

"Data": Click it to view historical data.

"Home": Click it to back to home interface .

2.0 "CT in Small Range" : In green once it's selected,IK is 50/5

"CT in Large Range" : In red once it's selected, IK(CT ) UK(PT) refer to value displayed on screen.

 

2. No-load/Load Manual Test

HM505002

Interface Description:

 "500V 1000V, 2000V, 3000V" : After choose the test voltage in parameter set interface (Figure 18), the chosen one will be in green.

 "Current ↑ " : Step up current manually

 "Current ↓": Step-down current manually

 "Timing": Click it to begin timing. This function only be used in temperature rise test .

 "Stop": Click it , voltage regulator back to Zero .

 "Home": Click it to back into to previous interface.

 

3.No-load/Load Auto Test

HM505001

Interface Description:

 "A Output Current" " B Output Current" " C output Current" : It means current from step-up voltage transformer to tested object.

 "Voltage Output" "AB Voltage "AC Voltage" "BC Voltage": Real-time display input voltage to tested object.

 "Keep Time": Withstand current time

 "Run Time" : It means the time from click Start to step up current until current back to Zero.

 "Start ": Click it to step-up current automatically

 "Stop":Click it to step-down current automatically , voltage regulator back to Zero

 "Home": Click it to back to previous interface.

 

Products Description

 

01

02

03

 

product-798-1044

07

03

10

11

12

13

15

 