Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of dc hipot test set in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.
Product Video
60kV 2mA DC Hipot Generator Operation Video
Products Description

ZGF-60kV DC high-voltage Tester is a technological product of the new era, suitable for DC high-voltage testing and DC leakage current testing of zinc oxide lightning arresters, demagnetization lightning arresters, power cables, generators, transformers, and switches in power departments, research institutions, railway stations, power plants, chemical plants, and other places.
Main Parameters
|
Specification |
60/2/3 |
120/2/3/5 |
60/5 |
200/2/3 |
300/2/5 |
|
Technical Parameter |
|
|
|
|
|
|
Output voltage((kV) |
60 |
120 |
60 |
200 |
300 |
|
Output current (mA) |
2/3 |
2/3/5 |
5 |
2/3 |
2/5 |
|
Output power (W) |
120/180 |
240/360/600 |
400 |
400/600 |
600/1500 |
|
Charging current(mA) |
3/4.5 |
3/4.5/6.5 |
5 |
3/4.5 |
3/7.5 |
|
Controller Case weight (kg) |
10.1 |
13 |
13 |
13.1 |
13.1 |
|
Dimension of multi-voltage tube (mm) |
Φ 90 |
Φ 90 |
Φ 110 |
Φ 110 |
Φ 110 |
|
× 380 |
× 470 |
× 530 |
× 910 |
× 1200 |
|
|
Height of multi-voltage tube (kg) |
2.3 |
3.2 |
4 |
8.0 |
10 |
|
Voltage measuring accuracy |
1.0%(full scale)± 1character, max resolution 0.1%kV |
||||
|
Current measuring accuracy |
1.0%(full scale)± 1character, max resolution 0.1%uA |
||||
|
Over voltage rectify accuracy |
≤ 1.0% |
||||
|
0.75 switch over accuracy |
≤ 0.5% |
||||
|
Ripple factor |
≤ 0.5% |
||||
|
Work manner |
Intermittent service; 30min of rated load; 1.1 times of rated voltage use: 10min |
||||
|
Temperature |
-10℃-40℃ |
||||
|
Relative humidity |
When at 25C, no more than 85%(no condensation) |
||||
|
Altitude |
Below 1500m |
||||
|
Capacitance load |
The capacitance of test object is no limit |
||||
|
Construction feature |
Electric insulation multivoltage tube |
||||
|
Air insulation,no leakage |
|||||
Product Description
|
1.Wiring:
Connect HV multivoltage tube with ground wire, cable wire, power wire and discharge rod wire as Figure 1
Note: 1). HV multivoltage tube ,Host, test object, must be connected to the same ground. 2). The high-voltage test wire must be suspended, no mopping is allowed. 3). The current limiting resistor must be connected when do capacitive test,Prevent damage to equipment and test object caused by excessive feedback current.
2.Panel description
Figure 2 1).Operating instruction of panel for control unit Open power switch(the potentiometer must be reset to zero),the screen will show as like figure 2. Pressing down the panel" function" button to choose screen "DC HV generator" , than pressing down pane "start/stop" button ,the screen will be show as figure 3
Figure 3 "IN" is the wired test mode,"IE" is wireless mode.(note:This machine only supports wired mode,please select"IN". "U 0060KV" is that the test voltage can be set according to the test requirements. Operation step as below: First ,pressing down panel "function" button to choose the setting voltage value you need. You can choose to adjust voltage value with pressing down panel "increase/timing" (The current setting method is the same as the voltage setting method). Second, when finish set, press down panel "start / stop " button to exit setup mode. If back to home page, please press screen "function" button and choose "exit", if keeping test please choose screen "start" ,than the screen will show as Figure 4, rotate the panel potentiometer to boost voltage.
Figure 4 On the screen , "T1" is total time of test,"T2" is segmented timing (Press the panel "increase/timing" during the testing to time the trial for a period of time,press down panel "start / stop" button to exit segmented timing). "BU" is protection voltage (maximum voltage) "R" is Insulation resistance value,for reference. Note:Doing zinc oxide arrester test,after the current reach to 1mA, Press the "0.75UDC1mA storage" button to automatically reduce the voltage to 75% and show the leakage current of zinc oxide arrester. After the test , test data can be saved by pressing the button "0.75UDC1mA storage".To exit, press "start/stop". |
Hot Tags: dc hipot test set, China dc hipot test set manufacturers, factory, ac dielectric withstanding voltage check instrument, dc insulation inspection tester, dc hipot tester for product inspection, ac electrical component safety tester, ac dielectric withstanding voltage instrument, dc hipot tester for research use