DC Hipot Test Set

DC Hipot Test Set

ZGF-60kV DC high-voltage generator is a technological product of the new era, suitable for DC high-voltage testing and DC leakage current testing of zinc oxide lightning arresters, demagnetization lightning arresters, power cables, generators......
Send Inquiry
Description
Technical Parameters

Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of dc hipot test set in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.

 

Product Video

 

 

60kV 2mA DC Hipot Generator  Operation Video

 

 

 

Products Description

 

60kV 2mA 04

 


ZGF-60kV DC high-voltage Tester is a technological product of the new era, suitable for DC high-voltage testing and DC leakage current testing of zinc oxide lightning arresters, demagnetization lightning arresters, power cables, generators, transformers, and switches in power departments, research institutions, railway stations, power plants, chemical plants, and other places.

 

 

Main Parameters

 

 

Specification

60/2/3

120/2/3/5

60/5

200/2/3

300/2/5

Technical Parameter

 

 

 

 

 

Output voltage((kV)

60

120

60

200

300

Output current (mA)

2/3

2/3/5

5

2/3

2/5

Output power (W)

120/180

240/360/600

400

400/600

600/1500

Charging current(mA)

3/4.5

3/4.5/6.5

5

3/4.5

3/7.5

Controller Case weight (kg)

10.1

13

13

13.1

13.1

Dimension of multi-voltage tube (mm)

Φ 90

Φ 90

Φ 110

Φ 110

Φ 110

 

× 380

× 470

× 530

× 910

× 1200

Height of multi-voltage tube (kg)

2.3

3.2

4

8.0

10

Voltage measuring accuracy

1.0%(full scale)± 1character, max resolution 0.1%kV

Current measuring accuracy

1.0%(full scale)± 1character, max resolution 0.1%uA

Over voltage rectify accuracy

≤ 1.0%

0.75 switch over accuracy

≤ 0.5%

Ripple factor

≤ 0.5%

Work manner

Intermittent service; 30min of rated load;

1.1 times of rated voltage use: 10min

Temperature

-10℃-40℃

Relative humidity

When at 25C, no more than 85%(no condensation)

Altitude

Below 1500m

Capacitance load

The capacitance of test object is no limit

Construction feature

Electric insulation multivoltage tube

 

Air insulation,no leakage

 

Product Description

 

1.Wiring:

60-2

        Connect HV multivoltage tube with ground wire, cable wire, power wire and discharge rod wire as Figure 1 

 

Note:

1). HV multivoltage tube ,Host, test object, must be connected to the same ground.

2). The high-voltage test wire must be suspended, no mopping is allowed.

3). The current limiting resistor must be connected when do capacitive test,Prevent damage to equipment and test object

caused by excessive feedback current.

 

2.Panel description

60-2

Figure 2

1).Operating instruction of panel for control unit

   Open power switch(the potentiometer must be reset to zero),the screen will show as like figure 2.

   Pressing down the panel" function" button to choose screen "DC HV generator" , than pressing down pane "start/stop" button ,the screen will be show as figure 3

60-21

 Figure 3

 "IN" is the wired test mode,"IE" is wireless mode.(note:This machine only supports wired mode,please select"IN". "U 0060KV" is that the test voltage can be set according to the test requirements. Operation step as below:

   First ,pressing down panel "function" button to choose the setting voltage value you need. You can choose to adjust voltage value with pressing down panel "increase/timing" (The current setting method is the same as the voltage setting method).

  Second, when finish set, press down panel "start / stop " button to exit setup mode. If back to home page, please press screen "function" button and choose "exit", if keeping test please choose screen "start" ,than the screen will show as Figure 4, rotate the panel potentiometer to boost voltage.

60-22

Figure 4

  On the screen , "T1" is total time of test,"T2" is segmented timing (Press the panel "increase/timing" during the testing to time the trial for a period of time,press down panel "start / stop" button to exit segmented timing). "BU" is protection voltage (maximum voltage) "R" is Insulation resistance value,for reference.

  Note:Doing zinc oxide arrester test,after the current reach to 1mA, Press the "0.75UDC1mA storage" button to automatically reduce the voltage to 75% and show the leakage current of zinc oxide arrester.

After the test , test data can be saved by pressing the button "0.75UDC1mA storage".To exit, press "start/stop".

Hot Tags: dc hipot test set, China dc hipot test set manufacturers, factory, ac dielectric withstanding voltage check instrument, dc insulation inspection tester, dc hipot tester for product inspection, ac electrical component safety tester, ac dielectric withstanding voltage instrument, dc hipot tester for research use