AC Resonant Testing System with Partial Discharge Measurement for Cable Testing Laboratories
Cable testing laboratories require high-voltage test systems capable of handling different cable lengths, insulation types, voltage classes, and test procedures. For high-capacitance cable specimens, an AC resonant testing system offers an effective solution for generating the required AC test voltage while reducing the input power requirement.
When integrated with partial discharge (PD) measurement equipment, the system provides two important testing capabilities: AC withstand voltage testing and discharge activity monitoring.
For cable manufacturers, power utilities, independent testing laboratories, and electrical engineering companies, the challenge is not simply selecting a high-voltage source. The complete system must match the cable capacitance, test voltage, frequency range, measurement requirements, laboratory environment, and test standards.
This article explains how to configure and evaluate an AC resonant test system with PD measurement capabilities for cable testing laboratories.
1. Laboratory Requirements: Beyond AC Withstand Testing
Cable insulation testing can involve several different objectives.
An AC withstand test evaluates whether the cable insulation can withstand the specified voltage for a defined duration without breakdown.
Partial discharge measurement provides additional information about localized electrical discharge activity that may occur within cable insulation, joints, terminations, or other insulation structures.
A laboratory conducting both tests needs a system that can:
Generate the required AC test voltage.
Operate with the capacitance of the cable specimen.
Maintain a suitable output waveform.
Measure the applied voltage accurately.
Support PD measurement and calibration.
Provide suitable grounding and shielding.
Record test parameters and measurement results.
The resonant power source and PD measuring system must be designed to work together. The performance of the complete setup depends on the test circuit, measurement components, connections, background noise, and test-object characteristics.
2. System Configuration: What Should Be Included?
A cable laboratory AC resonant and PD test system may consist of the following components.
Variable-Frequency Power Supply
The frequency converter supplies excitation power to the resonant circuit and allows frequency adjustment during system tuning.
Frequency adjustment helps the system reach resonance with different cable capacitances and reactor configurations.
Excitation Transformer
The excitation transformer raises the output voltage of the frequency conversion source and provides the required electrical isolation.
Its rating depends on the system design, input power, excitation voltage, and resonant circuit requirements.
High-Voltage Resonant Reactor
The reactor supplies the inductive component required to compensate for cable capacitance.
Depending on the required test voltage and capacitance range, reactors may be connected in series, parallel, or in other manufacturer-defined configurations.
High-Voltage Divider
The divider measures the applied test voltage and supplies a measurement signal to the control and monitoring system.
The measurement point and divider configuration should be appropriate for the test circuit.
PD Coupling Capacitor
The coupling capacitor provides a measurement path for partial discharge signals.
It is normally selected according to the test voltage, capacitance, frequency range, measurement circuit, and insulation requirements.
PD Measuring Impedance
The measuring impedance transfers discharge signals from the coupling circuit to the PD detector.
Its characteristics influence the measurement bandwidth and the behavior of the configured PD measurement circuit.
PD Detector and Analysis Software
The PD detector collects and analyzes discharge signals.
Depending on the system configuration, the software may display apparent charge, phase-resolved patterns, pulse activity, measurement trends, and test voltage information.
Control, Protection, and Grounding System
The control system manages voltage adjustment, frequency tuning, test timing, monitoring, and protection functions.
The grounding system, shielding arrangement, and interlocks are essential parts of the laboratory installation.
3. How Series Resonance Supports High-Voltage Cable Testing
Power cables are capacitive loads. When AC voltage is applied, the cable draws capacitive charging current.
The charging current can be calculated as:

Where:
(IC) = capacitive current
(f) = test frequency
(C) = cable capacitance
(U) = applied RMS voltage
The apparent reactive power required by a capacitive cable is:

For long cable sections, the capacitance can be substantial. A conventional test transformer may therefore require a large power rating to supply the necessary charging current.
In a series resonant system, the reactor inductance compensates for the cable capacitance.
The approximate resonant frequency is:

At resonance, the inductive reactance and capacitive reactance balance each other.
The system can generate the required high AC voltage while the external power supply mainly compensates for system losses.
This principle makes series resonant systems suitable for testing capacitive loads such as power cables, GIS, and other high-voltage equipment.
4. How to Calculate Cable Testing Capacity
One of the most important steps in selecting a resonant system is calculating the electrical load of the cable.
A laboratory should not select a test system based only on voltage rating.
The following parameters must be considered:
Cable voltage class
Cable length
Capacitance per unit length
Required test voltage
Test frequency
Available reactor inductance
Resonant circuit current
Test duration
Connection configuration
Example: Cable Capacitance Calculation
Assume a cable specimen has:
Capacitance per kilometer: 0.25 μF/km
Cable length: 2 km
The total capacitance is:

If the test voltage is 100 kV RMS and the operating frequency is 50 Hz:
![]()
This represents the capacitive reactive power associated with the cable at the assumed voltage and frequency.
A resonant system can significantly reduce the required input power compared with directly supplying this capacitive load through a conventional test transformer.
The actual resonant system rating must still be determined from the required test voltage, cable capacitance, frequency range, reactor configuration, losses, and operating conditions.
5. Integrating Partial Discharge Measurement
PD measurement is not simply an additional instrument connected to the high-voltage source.
It requires a properly configured measurement circuit and a suitable testing environment.
A conventional charge-based PD measurement system may include:
Test object
AC high-voltage source
Coupling capacitor
Measuring impedance
PD detector
Calibration pulse generator
Voltage measurement system
Grounding and shielding arrangement
The measurement circuit must be calibrated with the configured test object and measurement arrangement.
Calibration helps establish the relationship between the injected calibration charge and the measured signal.
For cable laboratories, the measurement setup should also account for attenuation, reflections, background interference, and the distributed characteristics of cable systems.
IEC 60270:2025 covers charge-based partial discharge measurement under AC voltage up to 500 Hz and DC voltage, including measurement quantities, circuits, calibration, and test procedures.
6. What Can PD Measurement Reveal During Cable Testing?
Partial discharge measurement provides information about localized discharge activity that may be associated with insulation defects or installation-related problems.
Typical areas of investigation include:
Cable Insulation
Discharge activity may be associated with internal voids, defects, contamination, or localized insulation stress.
Cable Joints
Joints can be important diagnostic points because installation quality, interface conditions, and insulation workmanship may influence discharge behavior.
Cable Terminations
Stress-control components, interfaces, and installation conditions may affect the electrical behavior of cable terminations.
Manufacturing Defects
Cable manufacturers may use PD measurement as part of quality evaluation and development testing, depending on the applicable product standard and test procedure.
Discharge Activity During Voltage Application
The laboratory may record PD inception voltage, extinction voltage, apparent charge, pulse activity, and phase-resolved patterns where these measurements are included in the test program.
PD measurement can provide diagnostic information, but the presence or absence of a detected signal must be interpreted in the context of the test circuit, measurement sensitivity, noise, calibration, and applicable acceptance criteria.

7. AC Withstand Testing and PD Monitored Testing
These two testing functions should be clearly distinguished.
AC Withstand Test
The cable is subjected to the specified AC voltage for the defined test duration.
The primary objective is to evaluate whether the insulation withstands the test voltage without breakdown.
PD Monitored AC Test
PD measurement is conducted while the cable is energized by the AC test system.
The laboratory can observe discharge activity during voltage application and evaluate the measured results according to the agreed test criteria.
Diagnostic PD Test
A dedicated PD test may involve a voltage ramp, multiple voltage levels, extended measurement periods, or additional diagnostic analysis.
The procedure depends on the test standard, laboratory requirements, cable type, and customer specification.
The AC resonant system can serve as the voltage source for these test programs, provided its operating characteristics are appropriate for the required test.
8. Test Frequency and Cable Length
The achievable cable length depends on the total cable capacitance and the operating conditions of the resonant system.
Higher test frequency increases capacitive current at a given voltage and capacitance:
![]()
Therefore, test frequency, reactor configuration, voltage, and capacitance are closely related.
A laboratory should calculate the required test frequency range based on the cable load rather than assume the system can test every cable length at a fixed frequency.
Variable-frequency systems offer flexibility for matching different capacitive loads.
For applicable after-installation tests of extruded cable systems, standards such as IEC 60840 and IEC 62067 provide test requirements that should be reviewed according to cable voltage class and the relevant edition.
Test voltage, duration, frequency, and acceptance criteria must be selected according to the actual cable test procedure.
9. Laboratory Background Noise and PD Measurement Quality
PD measurement quality is strongly influenced by electrical noise.
Even a well-designed PD detector may experience interference from:
Power supply switching noise
Ground loops
External electrical equipment
Corona from exposed high-voltage connections
Poor grounding
Measurement cable interference
Noise from the laboratory environment
A cable laboratory may therefore require a shielded test area, corona-free connections, suitable grounding, controlled instrument placement, and low-noise measurement components.
Before testing, background noise should be measured and recorded.
The laboratory should evaluate the complete measurement circuit under the intended operating conditions.
A claimed sensitivity value should not be treated as guaranteed performance for every cable, voltage, test environment, or measurement configuration.
10. How to Select the Right AC Resonant and PD Test System
For a cable testing laboratory, equipment selection should begin with the testing requirements.
Voltage Rating
Determine the maximum required test voltage and whether the system must support multiple cable voltage classes.
Cable Capacitance
Calculate the capacitance of the longest cable specimen or the maximum test load.
Reactor Configuration
Review the available inductance, connection options, current rating, and maximum test voltage for the planned configuration.
Frequency Range
Confirm that the system can achieve the required test frequency under the expected cable load.
PD Measurement Capability
Review the PD detector, coupling capacitor, measuring impedance, calibration method, measurement bandwidth, and software functions.
Measurement Sensitivity
Evaluate the specified measurement sensitivity under defined conditions.
The laboratory should consider background noise, cable characteristics, connection arrangement, and calibration.
Test Procedures and Standards
Identify the standards and customer specifications that apply to the intended cable testing program.
The equipment configuration should support the required test methods rather than simply list multiple standards on a product page.
Data Recording
Consider whether the laboratory needs:
Voltage records
Frequency records
Test duration
PD measurements
Calibration information
Phase-resolved patterns
Test reports
Data export
Safety and Installation
Review grounding, discharge, interlocks, protection systems, shielding, laboratory space, cable routing, and operator access.
11. Typical Cable Laboratory Applications
An AC resonant system with PD measurement capabilities can be used in several laboratory environments.
Power Cable Manufacturers
Manufacturers may use the system for cable insulation testing, product evaluation, and test programs involving cable accessories.
High-Voltage Cable Laboratories
Independent laboratories may use resonant systems for AC withstand testing and PD measurement on cable specimens and associated insulation components.
Power Utilities
Utility laboratories may use the system to evaluate cable condition, verify test requirements, and conduct specified acceptance or diagnostic testing.
EPC Contractors
Electrical engineering contractors may use cable testing systems for project testing, installation verification, and commissioning-related test programs.
Research and Development
Research laboratories may use the system to investigate insulation behavior, discharge activity, test voltage response, and cable insulation performance.
12. Goldhome AC Resonant and Partial Discharge Testing Solutions
Wuhan Goldhome Hipot Electrical Co., Ltd. provides high-voltage testing equipment for cable manufacturers, electrical testing laboratories, power utilities, and industrial electrical engineering companies.
Goldhome AC resonant test systems can be configured according to cable capacitance, required voltage, test frequency, reactor arrangement, laboratory conditions, and measurement requirements.
For a cable testing laboratory requiring both AC withstand testing and partial discharge measurement, the proposed configuration may include:
Variable-frequency power supply
Excitation transformer
High-voltage resonant reactor
High-voltage divider
PD coupling capacitor
PD measuring impedance
Partial discharge detector
Control and protection system
Grounding and shielding accessories
The final configuration should be based on the cable test parameters and required measurement performance.
Goldhome provides testing equipment solutions for different laboratory and field testing applications.
Website: https://www.goldhomehipot.com
Frequently Asked Questions
Can an AC resonant system perform partial discharge testing?
Yes. An AC resonant system can serve as the high-voltage source for PD measurement when configured with a suitable coupling circuit, PD detector, calibration system, grounding, and measurement arrangement.
Why is a resonant system suitable for cable testing?
Power cables are highly capacitive loads. Series resonance compensates for the cable capacitance, reducing the input power required to generate high AC test voltage.
How is the maximum cable length determined?
The maximum testable cable length depends on cable capacitance per kilometer, required test voltage, frequency, reactor configuration, system current, and operating limits.
Does a PD detector automatically guarantee low background noise?
No. PD measurement quality depends on the complete test setup, including the high-voltage source, grounding, shielding, measurement circuit, connection layout, and laboratory environment.
What standards are relevant?
Depending on the cable voltage class and testing stage, relevant references may include IEC 60270 for partial discharge measurement, IEC 60060 for high-voltage testing techniques, IEC 60840 and IEC 62067 for applicable high-voltage cable systems, and relevant IEEE 400 series guides for field cable testing.
The exact applicable edition and test procedure should be confirmed for the specific cable and test program.
Can the system perform withstand testing and PD measurement simultaneously?
Yes, where the system configuration and test procedure support PD monitoring during AC voltage application. The test voltage, duration, PD measurement configuration, and acceptance criteria should be established before testing.
Conclusion
An AC resonant testing system with partial discharge measurement capabilities provides cable testing laboratories with an integrated approach to high-voltage AC testing and insulation discharge monitoring.
The resonant power source addresses the electrical loading of capacitive cable specimens, while the PD measurement system provides additional information about discharge activity under test voltage.
Successful system selection requires more than matching the maximum voltage rating. Cable capacitance, length, test frequency, reactor configuration, PD calibration, background noise, measurement requirements, and applicable standards must all be considered.
By configuring the complete system around the laboratory's actual cable testing requirements, engineers can establish a practical testing platform for AC withstand tests, PD monitored tests, insulation evaluation, and cable test documentation.