HM-YDJW-300kVA/300kV PD-Free Power Frequency AC Hipot Tester

HM-YDJW-300kVA/300kV PD-Free Power Frequency AC Hipot Tester

HM-YDJW-300kVA/300kV power frequency AC hipot tester for high-voltage insulation withstand testing and partial discharge measurement. Includes a 300kVA test transformer and integrated power supply cabinet.
Send Inquiry
Description
Technical Parameters

Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of hm-ydjw-300kva/300kv pd-free power frequency ac hipot tester in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.

 

 

Products video

                                  

                                  

 

Products Description

 

 

logo2

The HM-YDJW-300kVA/300kV PD-free Power Frequency AC Hipot Tester is designed for high-voltage AC insulation withstand testing and partial discharge measurement.

The equipment is suitable for factory testing of electrical equipment with voltage levels below 300kV. According to the operation manual, its applications include transformer insulation withstand voltage testing and partial discharge measurement.

The complete test system consists of an operation desk, an integrated power supply cabinet, a 300kVA/300kV test transformer, a current-limiting resistor, and a capacitive voltage divider.

The integrated power supply cabinet combines the power isolation transformer, voltage regulator, isolation step-up filter, and power compensation components. This configuration provides the power supply and voltage adjustment functions required for the test transformer.

The system operates at power frequency of 50Hz and provides an AC output voltage adjustable from 0 to 300kV through the test transformer.

 

Products Features

 

  • 1. 300kVA Test Capacity

    The HM-YDJW test transformer has a rated capacity of 300kVA and a rated output voltage of AC 0–300kV.

    It is designed for high-voltage AC insulation withstand testing in factory environments.

    2. Integrated Power Supply Cabinet

    The power supply cabinet integrates several functional units:

    Power isolation transformer

    Voltage regulator

    Isolation step-up filter

    Power compensation unit

    The integrated arrangement provides the low-voltage power supply and adjustment functions for the high-voltage test transformer.

    3. Power Frequency AC Testing

    The system operates at 50Hz. The test transformer is single-phase and uses an insulated tank enclosure.

    The equipment is intended for power-frequency AC withstand voltage testing rather than variable-frequency resonant testing.

    4. Automatic and Manual Operation

    The operation desk supports automatic and manual test modes.

    In automatic mode, operators can configure three test stages, including the target voltage, voltage boost speed, and withstand time for each stage.

    Manual mode provides voltage boost and step-down operations through the control interface.

    5. System Partial Discharge Requirement

    The operation manual specifies that, under a shielded test environment and with the harmonic component of the test power supply below 5%, the partial discharge level of the complete system should be less than 10pC at rated voltage.

    This requirement describes the system-level partial discharge condition specified in the manual.

logo1

Products Parameters

 

Complete Test Transformer

Parameter Specification
Model HM-YDJW-300kVA/300kV
Structure Insulated tank enclosure
Number of phases Single-phase
Rated frequency 50Hz
Rated capacity 300kVA
Input voltage 1kV
Output voltage AC 0–300kV
Output current 1.0 (unit not specified in manual)

Integrated Power Supply Cabinet

Component Parameter Specification
Power isolation transformer Rated capacity 100kVA
Power isolation transformer Input voltage 400V
Power isolation transformer Output voltage 400V
Voltage regulator Rated capacity 100kVA
Voltage regulator Input voltage 380V
Voltage regulator Output voltage 0–400V
Voltage regulator Output current 250A
Isolation step-up filter Rated capacity 100kVA
Isolation step-up filter Input voltage 0–400V
Isolation step-up filter Output voltage 0–1kV
Power compensation Rated capacity 250kVA
Power compensation Rated voltage 400V

All power supply cabinet components operate at 50Hz.

Current-Limiting Resistor

Parameter Specification
Model HMRV-300kV/1-4
Rated frequency 50Hz
Rated voltage 300kV
Rated current 1A

Capacitive Voltage Divider

Parameter Specification
Model HMFRC-300kV/0.001uF
Rated frequency 50Hz
Nominal capacitance 1000pF
Rated voltage 300kV
Dielectric loss Less than 0.5%
Voltage ratio 687:1
Measuring accuracy 1.5 class

 

Products  display

 

01

02

 

03

 

Hot Tags: hm-ydjw-300kva/300kv pd-free power frequency ac hipot tester, China hm-ydjw-300kva/300kv pd-free power frequency ac hipot tester manufacturers, factory