GIS Partial Discharge Test System

GIS Partial Discharge Test System

Model: GTU-1200kVA/600kV; Number of phases: Single-phase; Frequency: 50 Hz; Number of stages: Single-stage; Rated input excitation voltage: 1000 V; Input current: 1200 A; Rated output voltage: 0–600 kV; High-voltage output current: 2 A; Impedance voltage: ≤15% (50 Hz); Waveform distortion rate: ≤3%; Insulation medium: SF6. High-Voltage Output Current: 2 A Impedance Voltage: ≤15% (50 Hz)
Send Inquiry
Description
Technical Parameters

 

 

Products video

 

Products Description

 

 

logo8

The HMGTU-1200KVA/600KV GIS test system primarily consists of a control system, a high-voltage power supply system, a test specimen interface system, and a low-voltage power supply system. When testing is conducted in an unshielded environment, the harmonic content of the test power supply is <5%. At rated voltage, the partial discharge level of the entire system is less than 2 pC, and at 80% of rated voltage, it is less than 1 pC. The unit connects to the test specimen via a dedicated interface in a single step, enabling the completion of withstand voltage and partial discharge tests on the specimen. The annual leakage rate of each sealed gas chamber is less than 0.5%.

 

Products parameters

 

1. GTU High-Voltage Test Transformer

The transformer consists of an excitation coil, a high-voltage coil, and a measurement winding (this winding is used only for equipment commissioning).

  • Model: GTU-1200kVA/600kV
  • Number of Phases: Single-phase
  • Frequency: 50Hz
  • Number of Stages: Single-stage
  • Rated Input Excitation Voltage: 1000V
  • Input Current: 1200 A
  • Rated Output Voltage: 0–600 kV
  • High-Voltage Output Current: 2 A
  • Impedance Voltage: ≤15% (50 Hz)
  • Partial Discharge Level: Less than 2 pC at 100% rated voltage;
  • Less than 1 pC at 80% rated voltage;
  • Waveform Distortion Rate: ≤3%
  • Operating Time: 30 minutes at rated current; continuous operation at 2/3 rated current with coil temperature rise ≤55K
  • Insulation medium: SF6
  • Construction: The high-voltage, partial discharge-free test transformer is housed in a separate metal enclosure equipped with a gas filling port, pressure gauge, pressure relief valve, and terminal blocks. The high voltage is connected to the system's high-voltage GIS via bowl-type insulators and a current-limiting protective reactor.
  • Insulation level: Withstands 1.1 times the rated voltage for one minute without any abnormalities.

logo3

 

 

Products FAQs

Q: What is the scope of application for this 600 kV test system?

A: It is suitable for factory testing of GIS systems rated at 252 kV and below.

Q: What are the partial discharge (PD) requirements for the entire system?

A: The partial discharge level of the entire system at rated voltage must be less than 2 pC; at 80% of rated voltage, it must be less than 1 pC.

Q: What are the sealing standards for the equipment gas compartments?

A: The annual leakage rate of each sealed gas compartment must be less than 0.5%.

Q: What items are included in the factory acceptance inspection of the equipment?

A: 1. Visual inspection; 2. SF6 seal leak test; 3. Turns ratio test; 4. DC resistance measurement of each winding; 5. External withstand voltage test; 6. Induced withstand voltage test; 7. Short-circuit impedance measurement; 8. System partial discharge measurement (≤2 pC for 10 minutes at 600 kV); 9. Waveform distortion measurement (<5%); 10. Measurement accuracy calibration (±1%).

Q: What is the production lead time for the equipment?

A: 45 working days after the technical agreement and commercial contract take effect.

 