Products Description
I.Test Transformer:

Input: connect with ouput terminals of the cabinet
Meter: connect with the meter of the cabinet
Signal: this is the HV current sigbal, connect with the HV current of the cabinet
PE: earth, at the bottom, picture as below

PE: at the base, bottom left corner, picture as below

II. HV voltage divider

Attention: After the pulse calibration is complete, wrap the grounding wire around the pole as shown in the figure above.

III.Coupling capacitor

Please connect correctly according to the diagram
Operation Description
1.Icon of GTU Test and Control System, and main interface:

2.Parameter setting of the system

Setting Description:
Test voltage: testing voltage you need
Withstand Time: ≤10 minutes at rated current; Continuous operation for≤30 minutes at 2/3 rated current
Boost speed: 100-3000V / S Maximum
Step-down speed: 100-3000V/s Maximum
Alarm voltage: when the testing voltage value is over the setted voltage, the main contactor will be turned off, the setted voltage setting value is 1.1 times of required testing voltage value
Alarm current: when the low voltage current value is over the setted low voltage current value, the main contactor will be turn off, test stops.
Flashover factor: Suggest 30% input, activate protection when voltage drops by more than 30%.