30kVA Triple Frequency Induction Test Set

30kVA Triple Frequency Induction Test Set

This device is primarily used to perform inductive withstand voltage tests on power equipment such as transformers and voltage transformers (PTs). By applying high-voltage alternating current at double the frequency (typically 150 Hz), it effectively evaluates the performance of the internal longitudinal insulation (such as turn-to-turn, layer-to-layer, and section-to-section insulation) within the equipment’s windings. This is a critical test for ensuring the safe operation of the equipment.
Send Inquiry
Description
Technical Parameters

Products overview

 

30kva02

This device is primarily used to perform inductive withstand voltage tests on power equipment such as transformers and voltage transformers (PTs). By applying high-voltage alternating current at double the frequency (typically 150 Hz), it effectively evaluates the performance of the internal longitudinal insulation (such as turn-to-turn, layer-to-layer, and section-to-section insulation) within the equipment's windings. This is a critical test for ensuring the safe operation of the equipment.

 

Products Parameters

 

  • Input Voltage: 380V/Three-phase
  • Rated Capacity: 30kVA
  • Input Current: 45.5A
  • Output Voltage: 0–400V
  • Output Current: 43.3A
  • Current Output Indication: 50A (Low-voltage current input from three-phase test transformer)
  • High-Voltage Output Indication: 30 kV (high-voltage output of three-phase test transformer)
  • Meter Accuracy: Class 1.5 (analog)
  • Overcurrent Setting: 0–50 A (protects the low-voltage input of the three-phase test transformer)
  • Overcurrent Bounce Release Time: 7 ms
  • Timing range: 0–999 s, min, h (switchable)
  • Cooling method: Natural cooling

30kva01

 

Hot Tags: 30kVA Triple Frequency Induction Test Set, China 30kVA Triple Frequency Induction Test Set manufacturers, factory