How to Perform a TTR Test on a Transformer?
A Transformer Turns Ratio (TTR) test verifies that the transformer's measured turns ratio agrees with its rated/nameplate ratio. It is commonly performed during transformer commissioning, routine maintenance, after repairs, and when investigating winding or tap-changer problems.

1. Isolate and Prepare the Transformer
Before connecting the TTR tester:
De-energize the transformer.
Isolate it from all power sources.
Apply the required grounding and safety procedures.
Verify that the transformer is completely de-energized.
Disconnect external connections as required by the test procedure.
Check the transformer nameplate for rated voltages, winding configuration, and tap positions.
Never connect a TTR tester to an energized transformer.
2. Select the Correct Test Connections
Connect the TTR tester to the appropriate transformer terminals according to the winding configuration.
For example, on a three-phase transformer, the tester may measure the ratio between the HV and LV windings phase by phase.
The exact connection depends on:
Transformer vector group
Wye (Y) or delta (Δ) connection
Number of phases
Available neutral terminals
Tap-changer configuration
Manufacturer's test procedure
Always follow the TTR instrument manufacturer's connection diagram and the transformer's test requirements.
3. Connect the TTR Tester
Connect the tester's excitation and measurement leads to the transformer terminals.
A typical test setup is:
TTR Tester → HV winding → Transformer magnetic core → LV winding
The tester applies a controlled AC test voltage to one winding and measures the induced voltage on the other winding.
4. Enter Transformer Nameplate Data
Modern TTR testers generally allow the operator to enter or select:
Rated HV voltage
Rated LV voltage
Transformer phase configuration
Vector group
Tap position
Expected turns ratio
The tester can then calculate the expected ratio and compare it with the measured value.
5. Perform the Ratio Measurement
Start the test from the TTR tester.
The instrument measures the voltage ratio and typically displays:
Measured turns ratio
Expected/rated ratio
Ratio deviation (%)
Phase angle
Excitation current
Polarity/vector relationship, depending on the instrument
A simplified deviation calculation is:
Ratio Deviation (%) = (Measured Ratio − Rated Ratio) / Rated Ratio × 100
The acceptable limit should be determined according to the applicable standard, transformer manufacturer's specifications, and project requirements rather than applying one universal value to every transformer.
6. Test All Phases
For a three-phase transformer, perform the test on all relevant phases.
For example:
Phase A → Phase a
Phase B → Phase b
Phase C → Phase c
The measured ratios should be consistent with the transformer's rated ratio and expected phase relationship.
Significant differences between phases can indicate a potential winding, connection, or tap-changer problem.
7. Test the Tap Positions
If the transformer has a tap changer, perform measurements at the specified tap positions.
For example:
Tap +5 → Test
Tap +2.5 → Test
Tap 0 → Test
Tap −2.5 → Test
Tap −5 → Test
The ratio should change according to the designed tap characteristics.
For an OLTC, additional tests such as dynamic resistance measurement may be required when investigating contact or switching problems.
8. Analyze the Results
- Compare the measured results with:
- Transformer nameplate data
- Factory test report
- Previous maintenance test results
- Manufacturer specifications
- Applicable standards
TTR Test vs. Winding Resistance Test
It's useful to perform both tests because they identify different problems:
| Test | Main purpose |
|---|---|
| TTR | Verify winding/voltage ratio and phase relationship |
| DC Winding Resistance | Check winding resistance, connections and OLTC contacts |
| Insulation Resistance | Evaluate insulation resistance |
| Tan Delta | Evaluate dielectric losses and insulation condition |
















