Transformer Test Bench

Transformer Test Bench

The Transformer Test Bench is an integrated, multi - functional dedicated testing device designed for comprehensive performance evaluation and quality assessment of power transformers and distribution transformers.
Send Inquiry
Description
Technical Parameters

Product Overview 

 

IMG7405

The HM5050 Transformer Test Bench is an integrated, multifunctional specialized testing device designed specifically for the comprehensive performance evaluation and quality inspection of power transformers and distribution transformers. Its primary applications include:

Power system maintenance: Testing basic parameters such as no-load loss, load loss, DC resistance, turn ratio, and winding group.

 

 

 

Test item

 

  • Effective value of three-phase voltage
  • Effective value of three-phase current
  • Three-phase active loss
  • Three-phase reactive loss
  • Three-phase average voltage
  • Three-phase mean voltage value
  • Three-phase mean current value
  • Total power
  • No-load current percentage
  • Impedance voltage percentage
  • Frequency
  • Power factor

IMG7409

 

 

 

Technical Specifications

 

Test Item

Parameter Range/Capability

DC Resistance Test

0.1mΩ–20kΩ, resolution 0.1μΩ

Turns Ratio & Winding Group Test

Ratio range 1–10000, accuracy ±0.1%

No - load/Load Loss Test

Voltage 0–1000V, current 0–100A

Power Frequency Withstand Test

0–80kV, adjustable overcurrent protection threshold

Partial Discharge Test

Sensitivity ≤5pC, frequency band 10kHz–1MHz

Insulation Performance Test

Automatic calculation of absorption ratio & polarization index

Lightning Impulse Test

Standard waveform (1.2/50μs), peak ≤200kV

 

Maintenance FAQs

 

Q: The device shows no display when powered on. How to troubleshoot?

A: Check power cable connections and input voltage. If unresolved, contact after - sales service for internal fuse or motherboard inspection.

Q: Frequent alarms during withstand voltage tests. Possible causes?

A: Likely due to poor insulation of the tested transformer or loose test leads. Reconnect wires and inspect the transformer.

Q: Large deviation in turns ratio test results. How to calibrate?

A: Enter calibration mode and follow the manual to adjust parameters using a standard resistance box.

Q: How to clean the device surface?

A: Use a dry, soft cloth. Avoid alcohol, corrosive solvents, or liquid penetration.

Q: Precautions for first use after long - term storage?

A: Inspect cables, preheat with no - load operation for 10 minutes, and run self - diagnostics.

 

Note: Follow the user manual for operations. Regular professional calibration ensures accuracy and safety.

 

Optimized for SEO Keywords: Transformer Testing Equipment, Comprehensive Transformer Test Bench, High - Voltage Test Bench, Transformer Diagnostic Tools.

 

Hot Tags: transformer test bench, China transformer test bench manufacturers, factory, high voltage testing laboratory, ac hipot tester for product inspection, 200kV 2mA DC Hipot Tester, high voltage test chamber, high voltage testing diode, ac electrical safety inspection instrument