- Power Control Cabinet CHXB-15kW/220/380V:
- Rated Power: 15kW
- Input Voltage: Single-phase 220V ±15% or Three-phase 380V, 50Hz
- Output Voltage: 0–400V adjustable
- Output Frequency: 30–300Hz, adjustable in 0.1Hz increments, frequency instability ≤0.02%
- Output Current: 0–37.5A
- Excitation Transformer JLB-15kVA/1.5/3/6kV/0.4kV:
- Rated Capacity: 15kVA
- Input Voltage: 0–400V, single-phase
- Output Voltage: 1.5kV / 3kV / 6kV
- Output current: 10 A / 5 A / 2.5 A
- Construction: Dry-type
- High-voltage reactor DK-67.5kVA/27kV (6 sections):
- Rated operating voltage: 27 kV
- Rated operating current: 2.5 A
- Rated inductance: 50 H
- Continuous operating time: 60 minutes
- Temperature rise: Less than 60°C
- Operating Frequency: 30–300 Hz
- Capacitive Voltage Divider FRC-120kV/2000pF:
- Capacitance: 2000 pF
- Rated Voltage: 120 kV
- Operating Frequency: 30–300 Hz

Test Objection Specification
| No. | Test Specimen Type | Specifications | Maximum Capacitance | Test Voltage | Applicable Frequency Range |
| 1 | Power Cables | 10 kV, 300 mm² and below, max. 6 km | ≤2.106 μF | 22 kV | 30–300 Hz |
| 2 | Power Cables | 35 kV, 300 mm² and below, max. 3 km | ≤0.429 μF | 52 kV | 30–300 Hz |
| 3 | Electrical Equipment | Transformers, switches, current transformers, etc., rated at 35 kV and below | - | Up to 95 kV | 30–300 Hz |
Products Images

FAQs
Q: What are the maximum lengths of 10 kV, 35 kV, and 66 kV cables that this 324 kVA/108 kV unit can support? How should the reactors be configured?
A: For 66kV/300mm² cables, the maximum length is 1,000 m; for 35kV/300mm² cables, the maximum length is 1,000 m. Both configurations use four reactors arranged in a 2-in-series, 2-in-parallel combination. For 10kV/300mm² cables, the maximum length is 3,000 m, using four reactors in a fully parallel configuration.
Q: What scenarios are the 1.5kV, 3kV, and 6kV output settings of the excitation transformer suitable for?Q:WHAT
A: The 1.5kV setting is suitable for testing low-voltage cables with reactors in a fully parallel configuration; the 3kV setting is suitable for testing medium-voltage cables with reactors in a two-series-two-parallel configuration; the 6kV setting is suitable for testing high-voltage transformers/GIS with reactors in a fully series configuration, and can be flexibly switched according to the test voltage.
Q: What are the inductance, withstand voltage, and Q-factor of a single reactor? What is the Q-factor of the entire unit?
A: A single reactor has an inductance of 100 H ±5%, a power-frequency withstand voltage of 27 kV for 60 seconds, and a Q-factor of ≥30; the unit itself has a Q-factor of >50, and with cable load, the Q-factor is >30.