Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of series resonant test system in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.
Products Indication
- Power Control Cabinet CHXB-15kW/220/380V:
- Rated Power: 15kW
- Input Voltage: Single-phase 220V ±15% or Three-phase 380V, 50Hz
- Output Voltage: 0–400V adjustable
- Output Frequency: 30–300Hz, adjustable in 0.1Hz increments, frequency instability ≤0.02%
- Output Current: 0–37.5A
- Excitation Transformer JLB-15kVA/1.5/3/6kV/0.4kV:
- Rated Capacity: 15kVA
- Input Voltage: 0–400V, single-phase
- Output Voltage: 1.5kV / 3kV / 6kV
- Output current: 10 A / 5 A / 2.5 A
- Construction: Dry-type
- High-voltage reactor DK-67.5kVA/27kV (6 sections):
- Rated operating voltage: 27 kV
- Rated operating current: 2.5 A
- Rated inductance: 50 H
- Continuous operating time: 60 minutes
- Temperature rise: Less than 60°C
- Operating Frequency: 30–300 Hz
- Capacitive Voltage Divider FRC-120kV/2000pF:
- Capacitance: 2000 pF
- Rated Voltage: 120 kV
- Operating Frequency: 30–300 Hz

Test Objection Specification
| No. | Test Specimen Type | Specifications | Maximum Capacitance | Test Voltage | Applicable Frequency Range |
| 1 | Power Cables | 10 kV, 300 mm² and below, max. 6 km | ≤2.106 μF | 22 kV | 30–300 Hz |
| 2 | Power Cables | 35 kV, 300 mm² and below, max. 3 km | ≤0.429 μF | 52 kV | 30–300 Hz |
| 3 | Electrical Equipment | Transformers, switches, current transformers, etc., rated at 35 kV and below | - | Up to 95 kV | 30–300 Hz |
Products Images

FAQs
Q: What are the maximum lengths of 10 kV, 35 kV, and 66 kV cables that this 324 kVA/108 kV unit can support? How should the reactors be configured?
A: For 66kV/300mm² cables, the maximum length is 1,000 m; for 35kV/300mm² cables, the maximum length is 1,000 m. Both configurations use four reactors arranged in a 2-in-series, 2-in-parallel combination. For 10kV/300mm² cables, the maximum length is 3,000 m, using four reactors in a fully parallel configuration.
Q: What scenarios are the 1.5kV, 3kV, and 6kV output settings of the excitation transformer suitable for?Q:WHAT
A: The 1.5kV setting is suitable for testing low-voltage cables with reactors in a fully parallel configuration; the 3kV setting is suitable for testing medium-voltage cables with reactors in a two-series-two-parallel configuration; the 6kV setting is suitable for testing high-voltage transformers/GIS with reactors in a fully series configuration, and can be flexibly switched according to the test voltage.
Q: What are the inductance, withstand voltage, and Q-factor of a single reactor? What is the Q-factor of the entire unit?
A: A single reactor has an inductance of 100 H ±5%, a power-frequency withstand voltage of 27 kV for 60 seconds, and a Q-factor of ≥30; the unit itself has a Q-factor of >50, and with cable load, the Q-factor is >30.
Hot Tags: series resonant test system, China series resonant test system manufacturers, factory, innovative solutions for switchgear testing































