HMYDJW-20kVA/100kV AC Withstand Voltage Test Set

HMYDJW-20kVA/100kV AC Withstand Voltage Test Set

A complete 20 kVA, 100 kV power-frequency withstand voltage test set: oil-immersed test transformer, desk-type automatic console and all interconnecting hardware, supplied and commissioned as one system. 20 kVA capacity 0-100 kV AC 0-0.2 A output 27-inch touch screen PD-free configuration
Send Inquiry
Description
Technical Parameters

Wuhan Goldhome Hipot Electrical Co., Ltd. is one of the leading manufacturers and suppliers of hmydjw-20kva/100kv ac withstand voltage test set in China. With abundant experience, our factory offer high quality customized products made in China with competitive price. Welcome to contact us for quotation.

 

 

Products video

                    

 

Product Overview

 

logo6

 

The HMYDJW-20kVA/100kV applies an adjustable AC test voltage of up to 100 kV to transformers, bushings, insulators, cables and complete assemblies, for power-frequency withstand testing and for DC withstand or leakage current testing when a rectifier is fitted.

The console houses the regulating transformer and controls, delivering 0–380 V to the primary of the oil-immersed test transformer. The transformer steps this up to a continuously adjustable high voltage, so the test voltage is raised and lowered smoothly rather than in steps - an important detail when the specimen must never be switched at full voltage.

The set is configured without partial discharge sources in the high-voltage path, which makes it suitable where the test is judged on discharge behaviour and not only on breakdown.

20 kVA capacity

0–100 kV AC

27-inch touch screen

PD-free configuration

 

Key Product Features

 

 

Complete, matched system

Transformer, console and interconnecting hardware are selected for each other at the factory, so there is no integration work on site.

Automatic three-stage sequence

Each stage carries its own voltage setpoint, hold time and rate of rise; stages can be enabled independently.

Manual jog control

Raise and lower at 50–3000 V/s and 50–5000 V/s respectively, with a programmable upper voltage limit.

Layered protection

Over-voltage, leakage current and low-voltage current limits each open the main contactor; the emergency stop acts at any point of the sequence.

Zero-position interlock

The regulator returns to zero on power-up if it is not already there, and a test cannot start until the zero indicator is lit.

Test records to Excel

Filter stored results by date range and export the table directly, without transcribing readings by hand.

Technical Specifications

 

Electrical
Rated capacity 20 kVA
High voltage output 0–100 kV
High voltage current 0–0.2 A
Low voltage output 0–380 V
Low voltage current 0–52.6 A
Metering voltage 0–100 V
Supply AC 380 V ±10%, 50 Hz ±2 Hz
Measurement and control
Voltage meter accuracy 0.5% FS ±3 digits
Current meter accuracy 0.5% FS ±3 digits
Overall accuracy 4%
Timing range 0–999.9 s, extended-time mode available
Display 27-inch LCD touch screen
Rate of rise (manual) 50–3000 V/s, adjustable
Rate of fall (manual) 50–5000 V/s, adjustable
Return-to-zero rate 50–5000 V/s, adjustable
Test transformer
Type Single-phase, oil-immersed, single-frame core
Winding arrangement Primary on core, high-voltage winding outside (coaxial)
Design standard JB/T 9641-1999
Environment
Operating temperature 0–50 °C
Relative humidity ≤85% RH
Altitude Below 1000 m

 

Ordering information

 

Item Model Description
AC withstand voltage test set HMYDJW-20kVA/100kV Complete set: oil-immersed test transformer plus desk-type automatic control console
Test transformer YDJ 20kVA/100kV Oil-immersed, single-phase, single-frame core, 100 kV
Control console Desk type, 27-inch Automatic three-stage and manual jog modes, data logging
Current-limiting resistor R1 Selected per rating 0.5–1 Ω/V of test voltage for high-voltage output of 100–300 mA
Sphere gap Selected per rating Set to 110%–120% of test voltage; protective resistor about 1 Ω/V

 

FAQ

 

Q: What is the maximum output of the HMYDJW-20kVA/100kV?

A: The set delivers 0–100 kV AC at 0–0.2 A from a rated capacity of 20 kVA, with a low-voltage input range of 0–380 V at 0–52.6 A.

Q: What is included in the supply?

A: The oil-immersed test transformer and the desk-type automatic control console, together with the current-limiting resistor, sphere gap assembly and instrumentation described in the operating manual.

Q: Does the set run the test automatically?

A: Yes. The console runs a preset three-stage sequence with per-stage voltage, hold time and rate of rise, and also offers a manual jog mode with adjustable raise and lower rates.

Hot Tags: hmydjw-20kva/100kv ac withstand voltage test set, China hmydjw-20kva/100kv ac withstand voltage test set manufacturers, factory