Transformer Oil Dissolved Gas Analyzer (DGA): Working Principle, Fault Diagnosis And Selection Guide

Nov 17, 2026 Leave a message

 

Transformer Oil Dissolved Gas Analyzer (DGA): Working Principle, Fault Diagnosis and Selection Guide

Introduction

 

Power transformers operate under electrical and thermal stress throughout their service life. Over time, insulation materials and transformer oil may decompose due to overheating, electrical discharges, insulation deterioration or other abnormal operating conditions.

These processes can generate gases that dissolve in the insulating oil. Measuring and analyzing these gases provides valuable information about the internal condition of a transformer.

A Transformer Oil Dissolved Gas Analyzer (DGA) is an analytical instrument used to determine the concentrations of gases dissolved in transformer insulating oil. Gas chromatography is widely used for this purpose because it can separate and quantify individual gas components.

DGA testing is an important condition-monitoring method for power transformers, distribution transformers, reactors and other oil-filled electrical equipment.

This guide explains the working principle of a DGA analyzer, the main gases measured, common diagnostic methods and key equipment selection considerations.

 

1. What Is a Transformer Oil DGA Analyzer?

 

A Transformer Oil Dissolved Gas Analyzer is designed to measure gases dissolved in insulating oil and provide quantitative results, commonly expressed in microliters per liter (μL/L), which is numerically equivalent to parts per million by volume (ppm v/v).

The main purpose is to identify changes in gas concentration that may indicate abnormal conditions inside oil-filled electrical equipment.

Common applications include:

Power transformer condition monitoring

Distribution transformer maintenance

Transformer factory testing

Transformer commissioning and acceptance testing

Electrical utility maintenance laboratories

Oil-filled reactor and switchgear inspection

A laboratory DGA system generally combines several functional sections:

Oil sample introduction

Dissolved gas extraction

Gas separation

Gas detection

Data acquisition and processing

Result reporting and diagnostic support

The gas extraction and analytical stages work together. A reliable result depends not only on the chromatograph but also on the sampling procedure, extraction efficiency, calibration and data interpretation.

e1c7df1e3b23948f0531ceb7b82bdd4

 

2. Which Gases Does a DGA Analyzer Measure?

 

The most commonly measured transformer oil gases include hydrogen, methane, ethane, ethylene, acetylene, carbon monoxide and carbon dioxide. Oxygen and nitrogen may also be measured to provide additional information about the oil and transformer condition.

Gas Chemical Formula Typical Diagnostic Significance
Hydrogen H₂ May be associated with partial discharge and several electrical or thermal fault processes
Methane CH₄ Can be generated by thermal decomposition and some electrical discharge processes
Ethane C₂H₆ Often associated with lower-temperature thermal decomposition
Ethylene C₂H₄ Often associated with higher-temperature oil decomposition
Acetylene C₂H₂ Can indicate high-energy electrical discharge or arcing
Carbon Monoxide CO Associated with decomposition of cellulose-based insulation and other carbon-containing materials
Carbon Dioxide CO₂ Can provide information about paper insulation ageing and oxidation-related processes
Oxygen O₂ May help evaluate oil preservation and oxidation conditions
Nitrogen N₂ Can provide information about the transformer oil preservation system and gas conditions

The concentration of each gas is important, but the relationship between different gases is also useful.

For example, elevated acetylene may raise concern about electrical arcing, while increased ethylene may suggest thermal stress. However, these are diagnostic indicators rather than definitive fault conclusions.

Engineers should evaluate gas concentrations together with their rates of change, operating conditions, transformer history and other inspection results.

 

3. How Does a Transformer Oil DGA Analyzer Work?

 

A typical laboratory DGA analyzer uses gas extraction followed by gas chromatographic separation and detection.

Step 1: Transformer Oil Sampling

An oil sample is collected from the transformer using suitable sampling equipment, such as a gas-tight syringe or another approved sampling container.

Sampling quality is essential. Air contamination, gas loss, incorrect sample handling or unsuitable containers can affect the analytical result.

The sample should be properly identified with information such as:

Transformer identification

Sampling date and time

Sampling location

Oil type

Transformer operating condition

Reason for testing

IEC 60475:2022 provides guidance on sampling insulating liquids, including mineral oils and non-mineral insulating liquids.

Step 2: Dissolved Gas Extraction

The gases dissolved in transformer oil must be separated from the liquid before chromatographic analysis.

Common extraction methods include:

Vacuum extraction

A vacuum is applied to release dissolved gases from the oil. This method can be used in laboratory gas extraction systems.

Stripping extraction

A carrier gas is passed through the oil sample to remove dissolved gas components. The extracted gases are then transferred for analysis.

Headspace extraction

The oil sample is brought into contact with a controlled gas volume. Dissolved gases distribute between the oil and gas phases until the specified extraction conditions are reached.

The selected extraction method and its efficiency affect the accuracy of the final concentration results.

Step 3: Gas Chromatographic Separation

After extraction, the gas mixture enters the chromatographic column.

Different gas components interact differently with the column material. As a result, they move through the column at different rates and are separated before reaching the detector.

The separation process allows the analyzer to distinguish individual gas components rather than reporting only a total gas concentration.

Step 4: Gas Detection and Signal Processing

The separated gases reach the detector, which generates signals corresponding to the gas components.

Depending on the analyzer design, detector technologies may include:

Thermal conductivity detector (TCD)

Flame ionization detector (FID)

Other suitable detection arrangements

Different detector types have different response characteristics. A multi-detector configuration may be used to cover the required gas components.

The system processes the detector signals and calculates gas concentrations using calibration data.

Step 5: Result Display and DGA Report

The analyzer software processes the results and generates a report containing the measured gas concentrations.

A typical report may include:

Gas component names

Individual gas concentrations

Total combustible gas (if included in the configured reporting method)

Calibration information

Sample identification

Test date and time

Diagnostic charts or ratio calculations, if supported

The results can then be compared with previous measurements to evaluate changes in transformer condition.

 

4. How DGA Helps Identify Transformer Faults

 

DGA interpretation uses gas concentrations, gas ratios and historical trends to help identify possible internal problems.

Common diagnostic categories include:

Partial Discharge

Partial discharge involves localized electrical discharges that do not completely bridge the insulation between conductors.

Hydrogen is often an important gas in DGA assessment of partial discharge. Other gases may also be present depending on the discharge conditions and materials involved.

Thermal Faults

Thermal faults occur when oil or solid insulation is exposed to abnormal temperatures.

Different thermal conditions can produce different gas patterns. Ethane, methane and ethylene may contribute to the assessment of thermal decomposition.

Electrical Discharge and Arcing

High-energy electrical discharge can cause significant decomposition of insulating oil.

Acetylene is an important indicator in this assessment. Its presence and concentration should be evaluated alongside hydrogen and other gases.

Cellulose Insulation Degradation

Power transformers commonly use cellulose-based solid insulation, including paper and pressboard.

Carbon monoxide and carbon dioxide can be generated during the decomposition of cellulose insulation. Their concentrations and trends may help engineers assess possible insulation deterioration.

Gas Concentration and Trend Analysis

A single DGA result provides a snapshot of the transformer condition. Repeated testing provides additional information.

For example:

A gradual increase in a particular gas may indicate an ongoing process.

A rapid concentration increase may require prompt investigation.

A change in gas ratios may indicate a change in the suspected fault type.

Stable concentrations over time may provide useful evidence for condition assessment.

DGA should be interpreted together with transformer loading, operating temperature, maintenance history, electrical test results and other relevant information.

 

5. Common DGA Interpretation Methods

 

DGA analysis does not rely on gas concentration alone. Several interpretation methods are used in transformer condition assessment.

Key Gas Method

The key gas method evaluates the dominant gases associated with different fault processes.

It can provide an initial indication of possible thermal or electrical problems.

Rogers Ratio Method

The Rogers ratio method uses selected ratios between dissolved gases to help classify possible transformer fault conditions.

The method depends on valid gas measurements and applicable interpretation criteria. Not every gas combination produces a reliable classification.

Duval Triangle Method

The Duval Triangle method uses the relative proportions of selected gases to identify possible fault categories.

For the commonly used Duval Triangle 1, the three gases are methane (CH₄), ethylene (C₂H₄) and acetylene (C₂H₂).

The relative proportions are plotted on a triangular diagram to support fault interpretation.

Total Dissolved Gas and Trend Assessment

Total gas concentration and changes over time can provide additional information about transformer condition.

However, total dissolved gas concentration alone cannot identify the exact fault location or type. It should be considered alongside individual gas concentrations and other diagnostic information.

Important: DGA interpretation methods are diagnostic tools, not automatic proof of a particular fault. Final decisions should be made by qualified engineers using the applicable standard and the full operating history of the equipment.

 

6. Laboratory DGA Analyzer vs. Online DGA Monitoring System

 

DGA equipment is available in laboratory and online configurations. These systems serve different maintenance requirements.

Comparison Laboratory DGA Analyzer Online DGA Monitoring System
Sampling Oil samples collected manually Connected to the transformer for continuous or scheduled monitoring
Analysis Performed in a laboratory Performed by an installed monitoring unit
Monitoring Periodic Continuous or scheduled, depending on system design
Main Application Laboratory testing and maintenance programs Condition monitoring of selected operating transformers
Data Individual sample test reports Time-based gas concentration records and alarms, if supported
Installation Laboratory environment Installed at or connected to the transformer

When Should a Laboratory DGA Analyzer Be Used?

A laboratory analyzer is suitable for utilities, transformer manufacturers, independent testing laboratories and maintenance organizations that need to analyze oil samples from multiple transformers.

It can support periodic inspections, factory acceptance testing and follow-up investigations.

When Should an Online DGA System Be Used?

Online monitoring is useful when a transformer requires more frequent condition monitoring.

It can provide gas concentration trends and configured alarm information without requiring every measurement to be initiated through manual laboratory sampling.

However, the number of gases measured, sampling method, detection limits and alarm functions depend on the selected monitoring system.

 

7. How to Select a Transformer Oil DGA Analyzer

 

Selecting a DGA analyzer requires evaluating the analytical performance, extraction method, operating requirements and maintenance costs.

1. Measured Gas Components

Confirm which gases the system can measure.

A typical transformer DGA configuration includes H₂, CH₄, C₂H₆, C₂H₄, C₂H₂, CO and CO₂. Some configurations also measure O₂ and N₂.

2. Gas Extraction Method

The extraction system should provide suitable and repeatable gas recovery.

Confirm whether the analyzer uses vacuum extraction, stripping, headspace or another validated method.

3. Detection Range and Sensitivity

The instrument should cover the concentration ranges relevant to the intended transformer applications.

Check the detection limit, measurement range, repeatability and accuracy for each gas rather than relying on a single general accuracy figure.

4. Chromatographic Separation

The column configuration and detector arrangement should provide adequate separation of the required gas components.

Poor separation can affect the reliability of individual gas measurements.

5. Calibration and Quality Control

Calibration is essential for quantitative gas analysis.

A suitable DGA system should support calibration using appropriate standard gas mixtures and, where required, gas-in-oil reference samples.

The extraction and analysis process should be evaluated as a complete system.

6. Software and Reporting

Consider whether the software provides:

Automatic gas concentration calculations

Sample management

Historical data comparison

DGA trend charts

Gas ratio calculations

Diagnostic assistance

Report export

Diagnostic functions should be consistent with the standards and methods used by the laboratory.

7. Operating and Maintenance Requirements

Before purchasing, confirm carrier gas requirements, gas consumption, consumables, column replacement intervals, detector maintenance, calibration procedures and technical support.

These factors affect the long-term operating cost of the analyzer.

 

8. Relevant IEC Standards for Transformer Oil DGA

 

The following standards are important references for transformer oil sampling, gas analysis and interpretation.

Standard Scope and Application
IEC 60475:2022 Method of sampling insulating liquids
IEC 60567:2023 Sampling of free gases and analysis of free and dissolved gases in mineral oils and other insulating liquids
IEC 60599:2022 Interpretation of dissolved and free gas analysis in mineral oil-filled electrical equipment in service
IEC 63585:2026 Interpretation of DGA data in natural and synthetic ester insulating liquids

These standards address different stages of the DGA process.

IEC 60475:2022 provides guidance on collecting insulating liquid samples. IEC 60567:2023 covers gas sampling and analytical techniques, including gas extraction and chromatographic analysis. IEC 60599:2022 provides guidance for interpreting DGA results in mineral oil-filled equipment.

For ester-filled transformers, IEC 63585:2026 provides dedicated DGA interpretation guidance for natural and synthetic ester liquids. Its diagnostic criteria should not be assumed to be interchangeable with those for mineral oil.

The applicable standard should be selected according to the insulating liquid, equipment type and test purpose.

 

9. Why Sampling and Calibration Matter

 

A high-performance chromatograph cannot compensate for an incorrectly collected oil sample.

Several factors can affect DGA results:

Air entering the sample during collection

Gas escaping during storage or transportation

Incorrect sample containers

Contamination from sampling equipment

Delays before analysis

Incomplete gas extraction

Incorrect calibration

Unsuitable chromatographic separation

For this reason, DGA quality control should cover the entire process, from sampling to the final report.

IEC 60475:2022 provides specific guidance for insulating liquid sampling, while IEC 60567:2023 addresses gas extraction and analysis. These procedures should be incorporated into the laboratory's operating instructions.

 

10. Frequently Asked Questions

 

What is a transformer oil DGA analyzer used for?

It measures dissolved gases in transformer insulating oil. The results help engineers assess possible internal thermal faults, partial discharge, electrical discharge and insulation deterioration.

What gases are measured in transformer oil DGA?

Common gases include hydrogen, methane, ethane, ethylene, acetylene, carbon monoxide and carbon dioxide. Oxygen and nitrogen may also be included.

How does a DGA analyzer detect dissolved gases?

The system first extracts dissolved gases from the oil. The gas mixture is then separated through gas chromatography and measured by suitable detectors.

What is the difference between DGA and gas chromatography?

DGA is the analytical application and diagnostic process used to assess dissolved gases in insulating oil. Gas chromatography is a measurement technique commonly used to separate and quantify the individual gas components.

How often should transformer oil DGA testing be performed?

The testing interval depends on transformer importance, operating conditions, maintenance policy, previous DGA results and applicable utility requirements. Abnormal or rapidly changing results may require additional testing and investigation.

Can DGA identify every transformer fault?

No. DGA can provide important evidence of certain internal fault processes, but it cannot identify every defect or determine the exact fault location by itself. It should be combined with other electrical and physical inspection methods.

 

11. Transformer Oil Testing Solutions from Goldhome

 

Transformer oil analysis is an important part of electrical equipment maintenance and condition assessment.

Wuhan Goldhome Hipot Electrical Co., Ltd. provides electrical testing equipment and solutions for transformer manufacturers, power utilities, EPC contractors and testing laboratories.

Goldhome's transformer testing equipment portfolio includes transformer oil testing solutions and related electrical test systems. For laboratories establishing or upgrading a transformer oil testing workflow, the selection of DGA equipment should be matched to the required gas components, extraction method, analytical performance and applicable standards.

For more information about transformer testing equipment and electrical testing solutions, visit:

https://www.goldhomehipot.com

WhatsApp:+8618971538425

 

Conclusion

 

A Transformer Oil Dissolved Gas Analyzer is an important tool for evaluating the internal condition of oil-filled electrical equipment.

By combining proper oil sampling, dissolved gas extraction, chromatographic separation and quantitative detection, a DGA system provides valuable information about possible insulation and electrical problems.

When selecting a DGA analyzer, engineers should evaluate the measured gas components, extraction efficiency, detection performance, calibration requirements, software functions and applicable IEC standards.

Reliable DGA results depend on the complete analytical process, not only the chromatograph itself.