HMCXZ 108KVA108K AC Variable Frequency Resonant Test System Test Display Video
Product Overview

The 108kVA/108kV Variable Frequency Series Resonance Test System is mainly aimed at consumers 66kV,220kv cable design and manufacture , Reactor using separate design not only can meet high voltage, low current equipment test conditions request, and can satisfy the consumers' 10kV cable such as low voltage ac pressure test requirements. It Has a wide scope, earth, city and county level shall high-voltage test departments and electricity installation, repair engineering unit ideal compression test equipment.
The device is mainly Variable-frequency power source, Exciting transformer, High voltage reactor, Capacitive voltage divider composition.
Technical Parameters

Variable-frequency power source CHXB-10kW/220V/380V 1set
a)Rated output capacity:10kW
b)Working power:220V/380V,50 HZ
c)Output voltage:0 – 400V,single phase/30~300Hz
d)Rated input current:45.45A/26.3A
e)Rated output current :25A
f)Output waveform:sine wave
g)Voltage resolution:0.01kV
h)Voltage measurement accuracy:0.5%
i)Frequency adjustment range:30 – 300Hz
j)Frequency adjustment resolution:≤0.1Hz
k)Running time:Continuous working 60min under rated capacity
l)The highest temperature of components running continuously for 60min under rated m)capacity is no more than 65K
n) Noise level:≤50dB
High voltage reactor DK-27kVA/27Kv 4pcs
Rated capacity:27kVA
b) Rated voltage:27kV
c) Rated current:1A
d) Inductance:110H/pc
e) Quality factor:Q≥50 (f=45Hz)
f) Structure:dry-type
3) Exciting transformer JLB-10kvA/1.2kV/2.4kV/5kV/220V/400V 1set
a) Rated capacity:10kVA
b) Input voltage:220V/400V,single phase/20~300Hz
Input current: 45.45A/25A
c) Output voltage:1.2kV/2.4kV/5kV
d) output current: 8.33A;4.16A;2A
e)Structure:dry-type
Capacitive voltage divider FCR-120 kV -2000 pF 1set
a) Rated voltage:120kV
b) HV capacitance:2000PF
c) Dielectric loss:tgσ≤0.15%
d) Devide ratio:1000:1
e) measuring accuracy:1.5
5)Test wires and accessory 1set
panel Description

Signal: use to connect with the low voltage arm of the voltage divider,the largest voltage is 300V, input impedance is 10M.
Output: variable-frequency power source 0~400V/30~300Hz output terminal should be connected with exciting transformer input terminal.
Input: when the input voltage is three-phase 380V,please connect ABC,when the input voltage is single-phase 220V,please AC
PE: ground terminal,use to system safe grounding
LCD display: use to display parameter set,resonance,boost,time curve,Function status prompt,menu data and so on.
Printer: use to print test data.
Printer power:printer power switch
Reset: use to reset when occur such situation as load mistuning,variable-frequency power source overheat,and oter protect action.
Emergency stop: in the case of emergency,please press this button.
Power indicator:when power switch is open,the indicator light means power on
Power switch:power switch,when open,the power indicator light.
USB:can be connect with USB Flash Drive,transmission test data.
Hot tags:AC Series Resonant Test Device,Series Resonance Test Set,AC Series Resonant Test System,270kVA Variable Frequency Resonant Test Device,16200kVA/600kV Variable Frequency Series Resonance Tester,AC Resonant Test System with PD,Inductive Resonant Test System.HMCXZ-6000kVA/400kV Series Resonance Test Device