PD Variable Frequency Power Supply

PD Variable Frequency Power Supply

Partial-discharge-free variable-frequency power supplies can be used for AC withstand voltage tests and partial-discharge tests on all types of electrical equipment. By using an excitation transformer to drive a series or parallel resonant circuit, and adjusting the output frequency of the variable-frequency power supply, resonance is induced between the inductance L of the reactor in the circuit and the capacitance C of the test specimen; the resonant voltage is the voltage applied to the test specimen. Alternatively, the output can be fed directly to the primary winding of a transformer via an intermediate transformer to perform an inductive withstand voltage test.
Send Inquiry
Description
Technical Parameters

Product video

 

PD AC resonant test system Display Video

 

 

 

Products Overview

 

PD 01

Partial-discharge-free variable-frequency power supplies can be used for AC withstand voltage tests and partial-discharge tests on all types of electrical equipment. By using an excitation transformer to drive a series or parallel resonant circuit, and adjusting the output frequency of the variable-frequency power supply, resonance is induced between the inductance L of the reactor in the circuit and the capacitance C of the test specimen; the resonant voltage is the voltage applied to the test specimen. Alternatively, the output can be fed directly to the primary winding of a transformer via an intermediate transformer to perform an inductive withstand voltage test.

 

Key parameters

 

 

4.1 Rated Input Voltage: Three-phase AC 380 V ±10%, 50 Hz.

4.2 Rated Output Power: Single-phase 450 kW.

4.3 Output Frequency Range: 20 Hz to 300 Hz, continuously adjustable.

4.4 Rated Output Voltage: 0 to 350 V, continuously adjustable.

4.5 Rated Output Current: 0–1286 A, continuously adjustable.

4.6 Frequency Instability: ≤0.05%.

4.7 Voltage Instability: ≤1.0%.

4.8 Nonlinear distortion: ≤1%.

4.9 Partial discharge: ≤10 pC (measured on the high-voltage side of the step-up transformer).

4.10 Operating conditions: Temperature: –10°C to +45°C; Humidity: 10–90% RH; Altitude: ≤1000 meters.

4.11 Cooling method: Forced air cooling.

 

PD 01

On-site Test

 

 

20230912103258

20230912103255

20230912103252

 

Hot Tags: pd variable frequency power supply, China pd variable frequency power supply manufacturers, factory, professional high voltage testing tools, high voltage testing laboratory, high voltage testing inductor, ac resonance breaker testing system for ac resonance inductance testing system, ac resonance inductor bank testing system, ac resonance test equipment for ac resonance module testing