The Guide to detection methods for partial discharge induced voltage tests
Introduction
Partial discharge (PD) activity in high-voltage insulation systems is an important indicator of the occurrence of faults. Partial discharge induced voltage testing is a critical diagnostic procedure for evaluating the integrity of electrical installations such as transformers, cables, and switchgear systems. However, simply confirming the existence of PD is only half the job. The real challenge and focus of this guide is the accurate detection and location of the source of the discharge. Effective search and detection methods are extremely important for targeted maintenance, avoiding unplanned failures, and ensuring operational safety. This article discusses the most important techniques used to detect these invisible hazards.

Basic detection methodologies for locating PD
A multidimensional approach is often required to accurately locate PD sources. The following are the most common detection methods used during induced voltage testing:
1. Electrical detection method
This is the conventional and most direct approach. It involves connecting a measuring resistor in series with the test object in order to record the transient current pulses generated by each discharge.
Principle: PD pulses are high-frequency phenomena. Sensors such as coupling capacitors and high-frequency current transformers (HFCTs) are used to detect these pulses.
Application: Excellent for quantifying the apparent discharge load (measured in picoCoulombs) and determining the size of the discharge. It is a standard method for compliance testing.
Limitation: Although it confirms PD activity and its intensity, it provides limited information about the physical location of the source within large devices, especially if multiple sensors are present.
2.Acoustic emission (AE) detection
When partial discharge occurs, a pressure wave is generated-a microscopic acoustic emission or sound wave.
- Principle: Sensitive acoustic sensors (ultrasonic transducers) are placed on the outer surface of the equipment. These sensors detect the high-frequency sound waves (usually in the ultrasonic range above 20 kHz) produced by the discharge.
- Application: This method is particularly effective for locating PD sources in oil-filled transformers or gas-insulated switches. By using multiple acoustic sensors and analyzing the time difference of arrival (TDOA) of the sound signals, the exact spatial location of the PD can be triangulated.
- Advantage: Non-intrusive and provides excellent spatial resolution for fault location.
3.Ultra-High Frequency (UHF) Method
Partial discharges also emit electromagnetic waves within the ultra-high frequency spectrum (typically 300 MHz to 3 GHz).
Principle: Utilizes UHF sensors (with built-in or external antennas) to receive these electromagnetic signals. This method offers extremely high sensitivity and effectively resists low-frequency electrical noise generated by power supply systems.
Applications: Widely used for continuous monitoring in gas-insulated substations (GIS) and power transformers. Enables early detection of minute discharges.
Advantages: Combines high sensitivity with exceptional interference resistance, detecting partial discharge activity even when occurring deep within insulation systems.
The Importance of Multi-Method Detection
The most effective strategy for detecting and locating partial discharges typically requires the integrated use of multiple methods. For example:
First, electrical detection methods are employed to confirm the presence and intensity of partial discharges.
Subsequently, acoustic detection and ultra-high-frequency detection methods are applied simultaneously. Triangulation techniques are then used to determine the physical location of the defect.
This integrated approach fully leverages the strengths of each technology, significantly enhancing diagnostic reliability and accuracy while providing a comprehensive assessment of the insulator's health status.
The search for partial discharges during induced voltage testing is a complex undertaking that goes beyond simple verification. By understanding and applying various detection methods-electrical, acoustic, ultra-high frequency, and optical-engineers can go beyond simply identifying problems and pinpoint their location. This localization is a crucial step toward efficient and cost-effective maintenance that ensures the long-term reliability of critical high-voltage equipment. With advances in diagnostic technology, the integration of these methods is continually improving, enabling deeper insights into the condition of electrical insulation systems.