HM150 GIS Partial Discharge Free Simulation Test Display Video
Product Overview

Goldhome Hipot is a domestic manufacturer specializing in the production of GIS simulation equipment, offering premium services and high-quality products. Our newly designed HM150 Partial Discharge Simulation Unit saves space by integrating couplers and other components internally, thereby reducing costs.
Features & Advantages
1.Voltage, current, time, status information,andprompt messages displayed on a 27-inchlargescreen for clear and intuitive reading;
2.Full English /Chinese interface, simple and dearoperation, suitable for various applicationscenarios
3.All functions can be preset in advance, improvingproduct safety and reliability;
4.Status reminder function, fully Chinese-guided operation;
5.Emergency stop function:
During automaticcontrol, this feature enables emergency stops forwoltage incre ase or decrease at any point,
Automatic timing function.When automaticalycontrolled, when voltage rises automatically to theset value, thedevice starts timing; when the timedtime is up, the device automatically reduces voltageand returns to zero position.
6. Built in high-voltage measuring and partial discharge coupling capacitors
7. The partial discharge of the entire equipment is less than 3pC.
Technical Parameter

1.150kV/15kVA Partial Discharge-Free Transformer
Input Voltage: 0-380V
Input Current: 39.5A
Output Low Voltage: 0-150kV
Output Current: 0.1A
Partial Discharge at Rated Voltage ≤3Pc
2. Coupling Capacitor
Rated Low Voltage: 150kV
Rated Capacitance: 150pf
3. Discharge Model
4. Isolation Transformer
Rated Capacity: 15kVA
Input/Output Low Voltage: 380/380V
Structure: Mounted in system console
5. Control Console
1) Power Input: AC 380V
2) Power Output: AC 0–380V continuously adjustable
3) Rated Capacity: 15kVA
4) Rated Frequency: 50Hz
5) Operating Conditions: Indoor
Product Details
I.Structure Diagram
HM150 Partial Discharge Simulation Equipment Structural Detail Diagram

II.Console Operation Interface
Automatic Mode Diagram 1

Manual Mode Diagram 2

Alarm Parameter Diagram 3

Relevant test parameters must be set before starting the test.
Automatic Test Target Voltage: Setting range 0-150kV. In automatic mode, the voltage stabilizes and timing begins upon reaching this voltage.
Automatic Test Withstand Time: Setting range 0-9999S.
Automatic Test Voltage Rise Rate: Setting range 500-5000 V/s.
Automatic Test Voltage Drop Rate: Setting range 500-9999 V/s.
Manual Test Target Voltage: Setting range 0-150 kV. Once voltage is reached in manual mode, pressing the voltage increase button has no effect.
Manual Test Withstand Time: Setting range 0-9999 s.
Manual test voltage rise rate: Setting range 500-5000 V/s.
Manual test voltage fall rate: Setting range 500-9999 V/s.
Alarm voltage: Must exceed test target voltage. Setting range 0-160 kV. If high voltage exceeds set value, voltage regulator contactor disconnects.
Flicker coefficient: Setting range 30-99%. If high voltage fluctuation exceeds the set value, the voltage regulator contactor disconnects.
Low voltage current alarm: Setting range 0-40A. If the voltage regulator output current exceeds the set value, the voltage regulator contactor disconnects.
Clicking any discharge model button automatically moves the device to that position. Click the Rotate+ or Rotate- buttons for fine adjustment. During testing, clicking buttons is ineffective.
Products Description




Hot Tags: gis non partial discharge failure simulation test device,GIS Partial Discharge Free Simulator, Fault Simulation System For Converter Transformer,HMGTU AC High-Voltage Kit With Gas Type Partial Discharge.
Hot Tags: GIS PD Free Fault Simulation Device, China GIS PD Free Fault Simulation Device manufacturers, factory